Delta-electronics Network Device DVPPF01-S Manual de usuario

Busca en linea o descarga Manual de usuario para Hardware Delta-electronics Network Device DVPPF01-S. Delta Electronics Network Device DVPPF01-S User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 2
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Warning
This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and
wiring.
This is an OPEN TYPE Controller. The DVPPF01-S should be kept in an enclosure away from airborne dust, humidity,
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tool or key to open
the enclosure, so as to avoid the hazard to users or any damage to the module. DO NOT touch terminals when power
on.
Introduction
Functions
Cyclical data exchange process
Support the SYNC and FREEZE for data synchronization between master and slaves
Support Auto Baud rate detection
Support 12MHz baud rate in DP network
Cyclical data size is fixed to 4 bytes input and 4 bytes output
Support GSD file configures by using configuration tools
Product Profile
3
5
4
1
2
4
8
6
7
6
DVP-PF01
x16
x16
Model name
Extension port
Power/NET LED
Extension hole for mounting unit or module
DIN rail clip
Extension clip
Address switch
Profibus connector
Specifications
DP Connection
Interface DB9 pin connector
Transfer method High speed RS-485
Transfer cable 2-wire twisted shielded cable
Electrical isolation 500V DC
ENGLISH
Communication
Message types DPV0, cyclical data exchange process
Device ID 09B9 HEX
GSD file EATN09B9.GSD
Model name DVPPF01-S
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps
Baud rates
(auto detected)
1.5Mbps, 3Mbps, 6Mbps, 12Mbps
Environmental Specification
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Environment
Operation:C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)
IEC 61131-2 & IEC 68-2-27 (TEST Ea)
Approvals
Installation & Configuration
Dimensions
DVP-PF01
x16
x16
NET
POWER
1
0
Dimensions are in millimeter and [inch]
Installing the DVPPF01-S with the PLC Controller
Open the extension cover with a screwdriver. Use a screwdriver to lift and unfasten the fixing clip.
Connect the DVPPF01-S to extension port of PLC
controller and fasten the fixing clip.
Plug the Profibus connector to the socket of
DVPPF01-S, and tighten screw to secure the
connector.
0
1
STOP
DVP-12SA
RUN
RUN
BAT.LOW
ERROR
POWER
RS-232
RS-485
POWER
C0
X7
Y0
C1
Y1
Y2
Y3
C2
DVP-PF01
s
X1
X2
X0
X5
X4
X3
X6
s
NET
x16
x16
1
0
Cable Length and Baud Rate
The Maximum cable length in a segment depends on the transmission speed. Profibus-DP communicates at
speeds from 9.6kbps to 12Mbps over distances from 100 to 1,200 meters.
Baud rate (bps)
9.6k 19.2k 93.75k
187.5k
500k 1.5M 3M 6M 12M
Length (m) 1,200 1,200 1,200 1,000 400 200 100 100 100
Check the extension I/O by WPL software:
Connect to PLC MPU
Once connection is successful, software will check if 32
inputs/outputs is detected
PIN Definition of DP Connector
PIN Definition Content PIN Definition Content
1 -- N/C 6 VP Positive voltage
2 -- N/C 7 -- N/C
3 RxD/TxD-P
Data receiving/sending
P (B)
8 RxD/TxD-N
Data receiving/sending
N (A)
4 -- N/C 9 -- N/C
5 DGND
Data reference
potential (C)
1
5
9
6
MAC ID Setting
Address Content
1…0x7D Valid Profibus address
0 or
0x7E…0xFF
Invalid Profibus address. NET LED will rapidly blink with RED when
node address is at 0, 0x7E…0xFF
'
x16
'
x16
Setting of DVPPF01-S Connect to Profibus-DP
Connection example:
DVP-PF01
Profibus network
DVP-PS01
DVP-12SA
DVP-PF01
Y3
DVP-12SA
0
1
RS-232
RS-485
X4
RUN
STOP
C1
Y1
C2
Y2
X5
X6
Y0
C0
X7
RUN
POWER
BAT.LOW
ERROR
X2
X1
X0
s
s
X3
x16
x16
NET
POWER
PC Master
1
0
DVPPF01-S provides fixed 4 bytes input data and 4 bytes output data to user in Profibus-DP system. 4 bytes
input data are transmitted from DVPPF01-S module to Profibus-DP Master, it are mapping to Y20-Y57 in PLC
controller when DVPPF01-S is the first extension unit of PLC. 4 bytes output data are transmitted from
Profibus-DP Master, and it are also mapping to X20-X57 in PLC controller.
Data Mapping
Following is a ladder program example:
M1000
MOV
K4X20
D10
MOV
K4X40
D20
D21
K4Y40
K4Y20
D11
This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11
registers in PLC controller. And, PLC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57,
these 4 bytes data will send to DVPPF01-S, and DVPPF01-S will send these data to DP master.
Troubleshooting
NET LED
LED status
Indication Corrective actions
OFF No power supply Verify DVPPF01-S is powered on
Red blinking
(rapidly)
Invalid Profibus address setting
via switch
Check whether the switch setting is valid
Setting range of slave: 1-125
Set the valid value and re-power
Red blinking
Communication link to
PROFIBUS, and no cyclical
data exchanged
--
Red ON No connection to Profibus
Verify that DP network installation is OK
Verify that PLC is working
Verify that switch address setting match with configuration in
DP master
Green
blinking
Reserved --
Green ON
Cyclic data exchange in
progress and OK
--
Power LED
LED status Indication Corrective actions
Green ON Power on --
OFF No power Verify that PLC controller is powered on
(Open Type) /
( )
SYNC FREEZE
DP 12MHz
4 bytes 4 bytes
GSD file
3
5
4
1
2
4
8
6
7
6
DVP-PF01
x16
x16
/
NET
/
DIN
/
Profibus
DP
DB9
RS-485
2
500V DC
DPV0,
ID
09B9 HEX
GSD
DELT09B9.GSD
DVP-PF01
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps
1.5Mbps, 3Mbps, 6Mbps, 12Mbps
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
/
0°C ~ 55°C 50 ~ 95% 2
-25°C ~ 70°C 5 ~ 95%
/ IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)
IEC 61131-2, UL 508
DVP-PF01
x16
x16
NET
POWER
1
0
: mm [inches]
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - DVP-PF01

Warning  This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and wiring.  This

Pagina 2 - DVP -12 SA

 PLC DVP- PF01 01STOPDVP-12SARUNRUNBAT.LOWERRORPOWERRS-232RS-485POWERC0X7Y0C1Y1Y2Y3C2DVP-PF01sX1X2X0X5X4X3X6sNETx16x1610  Profibus-

Comentarios a estos manuales

Sin comentarios