English-2
Specifications
Voltage Class 230V Class
Model Number VFD-XXXF23X 007 015 022 037 055 075 110 150 185 220 300 370
Max. Applicable Motor Output (kW) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
Max. Applicable Motor Output (HP) 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50
Rated Output Capacity (kVA) 1.9 2.5 4.2 6.5 9.5 12.5 18.3 24.7 28.6 34.3 45.7 55
Rated Output Current (A) 5.0 7.0 11 17 25 33 49 65 75 90 120 145
Maximum Output Voltage (V)
Proportional to Input Voltage
Rated Frequency (Hz)
0.10-120.00Hz
Output Rating
Carrier Frequency (kHz) 4-10 3-9 2-6
Rated Input Current (A) 5.7 7.6 15.5 20.6 26 34 50 60 75 90 110 142
Rated Voltage 3-phase 180-264 V
Input
Rating
Frequency Tolerance 47 – 63 Hz
Voltage Class
460V Class
Model Number
VFD-XXXF43X
007 015 022 037 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600 1850 2200
Max. Applicable Motor
Output (kW)
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220
Max. Applicable Motor
Output (hp)
1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 250 300
Rated Output
Capacity (kVA)
2.3 3.2 4.2 6.5 10 14 18 25 29 34 46 56 69 84 114 137 168 198 236 281 350
Rated Output
Current (A)
2.7 4.2 5.5 8.5 13 18 24 32 38 45 60 73 91 110 150 180 220 260 310 370 460
Maximum Output
Voltage (V)
3-phase Proportional to Input Voltage
Output Frequency
(Hz)
0.10-120.00Hz
Output Rating
Carrier Frequency
(kHz)
4-10 3-9 2-6
3-phase Rated Input
Current (A)
3.2 4.3 5.9 11.2 14 19 25 32 39 49 60 73 91 120 160 160 200 240 300 380 400
Rated Voltage 3-phase 342-528 V
Voltage Tolerance -15~+10% (342-528 V)
Input Rating
Frequency
Tolerance
5% (47~63Hz)
General Specification
Control System SPWM (Sinusoidal Pulse Width Modulation, carrier frequency 2-10kHz)
Output Frequency Resolution 0.01Hz
Torque Characteristics Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz
Overload Endurance 120% of rated current for 1 minute
Accel/Decel Time 1-36000/0.1-3600.0/0.01-360.00 seconds (3 Independent settings for Accel/Decel Time)
V/f Pattern Adjustable V/f pattern
Control
Characteristics
Stall Prevention Level 20 to 150%, Setting of Rated Current
Keypad
Setting by
Frequency
Setting
External Signal
1 set of AVI analog voltage DC0-+10V/0-+5V, 2 sets of ACI analog current 0/4-20mA,
15 Multi-Function Inputs, RS-485 interface (MODBUS), External terminals UP/DOWN
Key
Keypad Set by RUN, STOP and JOG Operation
Setting
Signal
External Signal Operation by FWD, REV, JOG and communication operation
Multi-Function Input Signal
Multi-step selection 0 to 15, Jog, accel/decel inhibit, first to forth accel/decel switches,
counter, external Base Block (NC, NO), JOG, auxiliary motor start/maintenance
Multi-Function Output
Indication
AC Drive Operating, Frequency Attained, Desired Frequency Attained, Zero speed, Base
Block, Fault Indication, Local/Remote indication, and Auxiliary Motor Output
Operating Characteristics
Analog Output Signal 2 sets of Analog frequency/current signal output
Comentarios a estos manuales