AL# Attribute Content Explanation Default Latched
1 R/W Alarm point 2 0 Yes
2 R/W Alarm point 3 0 Yes
Symbol “R” refer to read only; “R/W” refers to read and write.
AL#0: Alarm Point 1
Explanations:
You can designate one RX extension point as the alarm point by setting up the AL register in IFD9507. When
the alarm point is triggered, IFD9507 will execute its corresponding function. When b15 of AL0 is set as “1”,
the Gateway will execute the event immediately. When RX point is triggered, the Gateway will only execute
the triggered event once.
Device Function Setting Attribute Default Latched
b15
Enabling the
function
b15 = 1: Enabling
b15 = 0: Disabling
R/W 0 Yes
b4 ~ b14 Reserved
R/W 0 No
b2 ~ b3
Type of event
enabled when
RX alarm point
is triggered
b3 b2
Reserved 0 0
Trigger E-Mail 0 1
Reserved 1 0
Reserved 1 1
The setting will be invalid when
thealarm function is being executed.
R/W 0 Yes
b1 Reserved Reserved
AL#0
b0
Condition for
triggering RX
b0 = 0: Triggered when RX input
point is low
b0 = 1: Triggered when RX input
point is high
R/W 0 Yes
AL#1: Alarm Output 2
Explanations:
The settings for AL#1 are the same as those in AL#0.
AL#2: Alarm Output 3
Explanations:
The settings for AL#2 are the same as those in AL#0.
4.4 In buffer registers (IN) in IFD9507
IN# Attribute Content Explanation Default Latched
0~255 R/W Data input buffer Ethernet/IP input data 0 No
Symbol “R” refers to read only; “R/W” refers to read and write.
Explanations:
The input data was sent to Ethernet.