Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
1-86 Revision January, 2008, Doc. Name: 2007PDD23000007
Mitsubishi FX Series PLC via Computer Link Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller Station number: 0.
Control area/status area: D0 / D10.
NOTE
1) This communication protocol supports FX series RS485 and RS232 communication module.
2) The default setting of this communication protocol is to support RS485 communication module. If the
user needs to use RS232 communication module, the user must change the communication setting from
RS485 to RS232 manually.
3) For more detailed information regarding the communication setting method, please refer to Mitsubishi
Communication User Manual named “User’s Manual - Data Communication Edition”.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No. Bit No.
Data length
Auxiliary Relay Mn n: 0-7679 N/A Word
Special Auxiliary Relay Mn n: 8000-8511 N/A Word
Status Relay Sn n: 0-4095 N/A Word
Input Relay Xn n: 0-377(octal) N/A Word
Output Relay Yn n: 0-377(octal) N/A Word
Timer PV Tn n: 0-255 N/A Word
16-bit Counter PV Cn n: 0-199 N/A Word
32-bit Counter PV Cn n: 200-255 N/A Double Word
Data Register Dn n: 0-7999 N/A Word
Special Data Register Dn n: 8000-8511 N/A Word
¾
Auxiliary Relay / Special Auxiliary Relay / Status Relay / Input Relay / Output Relay: Address must be
the multiple of 16.
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Auxiliary Relay Mn N/A n: 0-7679
Special Auxiliary Relay Mn N/A n: 8000-8511
Status Relay Sn N/A n: 0-4095