Delta Electronics Elevator Drive VFD-VL Especificaciones Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 141
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
Chapter 1 Introduction |DD Series
1-4
1-2 Preparation for Installation and Wiring
Install the AC motor drive in an environment with the following conditions:
Air Temperature:
-10 ~ +45°C (14 ~ 113°F)
Relative Humidity: <90%, no condensation allowed
Atmosphere pressure: 86 ~ 106 kPa
Installation Site
Altitude:
<1000m
Operation
Vibration:
<20Hz: 9.80 m/s
2
(1G) max
20 ~ 50Hz: 5.88 m/s
2
(0.6G) max
Temperature: -20°C ~ +60°C (-4°F ~ 140°F)
Relative Humidity: <90%, no condensation allowed
Atmosphere pressure: 86 ~ 106 kPa
Storage
Transportation
Vibration:
<20Hz: 9.80 m/s
2
(1G) max
20 ~ 50Hz: 5.88 m/s
2
(0.6G) max
Pollution Degree
2: can be used in a factory type environment.
Minimum Mounting Clearances
; The drive installation can be on a platform or on the wall. The left and middle figures show the
drive installation on a platform from the front and the side-view. The right figure shows wall
mounting. Both platform mounting and wall mounting are required to keep minimum mounting
clearances for good ventilation.
A B C D
20mm 15mm 20mm 8mm
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 140 141

Comentarios a estos manuales

Sin comentarios