Delta Electronics VFD007S23A Manual de usuario

Busca en linea o descarga Manual de usuario para Adaptadores E Inversores De Energía Delta Electronics VFD007S23A. Delta Electronics VFD007S23A User's Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 186
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente

Indice de contenidos

Pagina 2 - Preface

Chapter 1 Introduction|VFD-S Series Revision August 2006, SE08, SW V2.61 1-31.3 Installation Steps CASEHEAT SINKCOVERKNOB SCREWDIVISION PLATE Inst

Pagina 3 - CAUTION!

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-45 d20 Counter Reset: Parameter value d20 programs Multi-Function Input Term

Pagina 4

Chapter 5 Parameters|VFD-S Series 5-46 Revision August 2006, SE08, SW V2.61 d29 M0: 0: RUN 1: STOP, M1: no function, Direction is controlled by keyp

Pagina 5

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-47 Group 5: Multi-step speeds and PLC (Process Logic Control) parameters 5-0

Pagina 6 -

Chapter 5 Parameters|VFD-S Series 5-48 Revision August 2006, SE08, SW V2.61 Frequency60Hz50Hz40Hz30Hz20Hz15Hz10Hz0Hz5-095-105-115-125-135-145-15Pr.5-

Pagina 7

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-49 Example 3 (Pr. 5-07 = d3) Execute one cycle step by step: The example sho

Pagina 8 - Chapter 1 Introduction

Chapter 5 Parameters|VFD-S Series 5-50 Revision August 2006, SE08, SW V2.61 Example 5 (Pr. 5-07 = d1 Execute one cycle of the PLC program): In this e

Pagina 9 - 0160T007S23A

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-51 1234567WeightsBit0=Forward1=ReverseDirection of 1st Pr.5-00 =FWD speed fo

Pagina 10 - 1.3 Installation Steps

Chapter 5 Parameters|VFD-S Series 5-52 Revision August 2006, SE08, SW V2.61 Group 6: Protection Parameters 6-00 Over-Voltage Stall Prevention Unit

Pagina 11 - 1.4 Storage

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-53 DC bus voltagetimeOver-voltagedetectionlevel Pr.6-01OutputFreq.timeOver-v

Pagina 12

Chapter 5 Parameters|VFD-S Series 5-54 Revision August 2006, SE08, SW V2.61 6-03 Over-Torque Detection Mode (OL2) Factory Setting: d0 Settin

Pagina 13

Chapter 1 Introduction|VFD-S Series 1-4 Revision August 2006, SE08, SW V2.61DIVISION PLATESCREW Reinstall Division Plate. Screw Torque: 5 to 6 kgf-c

Pagina 14 - 2.2 Installation

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-55 1234560Hz or more50Hz10Hz5Hz020406080100120140160180 200Operationtime(min

Pagina 15

Chapter 5 Parameters|VFD-S Series 5-56 Revision August 2006, SE08, SW V2.61 d20 Software protection enable (codE) d21 Reserved d22 CPU f

Pagina 16 - 2.3 Dimensions

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-57 Group 7: Motor Parameters 7-00 Motor Rated Current Unit: 1 Settings

Pagina 17

Chapter 5 Parameters|VFD-S Series 5-58 Revision August 2006, SE08, SW V2.61 Group 8: Special Parameters 8-00 DC Braking Current Level Unit: 1 Sett

Pagina 18

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-59  DC Braking during Start-up is used for loads that may move before AC d

Pagina 19

Chapter 5 Parameters|VFD-S Series 5-60 Revision August 2006, SE08, SW V2.61  Following a power failure, the AC drive will start its speed search op

Pagina 20

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-61 8-15 Automatic Voltage Regulation (AVR) Factory Setting: d0 Sett

Pagina 21 - Frame S1: VFD007S21B

Chapter 5 Parameters|VFD-S Series 5-62 Revision August 2006, SE08, SW V2.61 Group 9: Communication Parameters 9-00 Communication Address Setting

Pagina 22

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-63 9-03 Time-out Detection Factory Setting: d0 Settings d0 Disable

Pagina 23

Chapter 5 Parameters|VFD-S Series 5-64 Revision August 2006, SE08, SW V2.61 Terminal Unit). Users can select the desired mode along with the serial

Pagina 24 - 5.0 [0.20]

Chapter 1 Introduction|VFD-S Series Revision August 2006, SE08, SW V2.61 1-53. If the AC motor drive is stored for more than 3 months, the tempera

Pagina 25 - Frame S2: VFD007S11A

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-65 Start bit0123456StopbitStopbit8-bit character11-bit character frame( 8.N

Pagina 26 - Frame S2: VFD007S11B

Chapter 5 Parameters|VFD-S Series 5-66 Revision August 2006, SE08, SW V2.61 3.2 ADR (Communication Address) Valid communication addresses are in the

Pagina 27

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-67 RTU mode: Command message: Response message: ADR 01H ADR 01H CMD 03H

Pagina 28

Chapter 5 Parameters|VFD-S Series 5-68 Revision August 2006, SE08, SW V2.61 ASCII Mode: Command message: Response message: STX ‘:’ STX ‘:’ ADR 1

Pagina 29 - 2.4 Wiring

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-69 ASCII mode: LRC (Longitudinal Redundancy Check) is calculated by summing

Pagina 30 - 2.4.1 Basic Wiring

Chapter 5 Parameters|VFD-S Series 5-70 Revision August 2006, SE08, SW V2.61 Step 5: Repeat step 3 and 4 until eight shifts have been performed. When

Pagina 31 - For VFDXXXSXXA/B/D/U

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-71 Content Address Functions Bit 0-1 00: No function 01: Stop 10: Run 11

Pagina 32 - NPN (sink mode)

Chapter 5 Parameters|VFD-S Series 5-72 Revision August 2006, SE08, SW V2.61 Content Address Functions 35: Reserved 36: PID error (Pld) 37: Reserve

Pagina 33 - PNP (source mode)

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-73 Example of an exception response of command code 06H and exception code 0

Pagina 34 - 2.4.2 External Wiring

Chapter 5 Parameters|VFD-S Series 5-74 Revision August 2006, SE08, SW V2.61 3.7 Communication program of PC: The following is a simple example of how

Pagina 35

Chapter 1 Introduction|VFD-S Series 1-6 Revision August 2006, SE08, SW V2.61This page intentionally left blank.

Pagina 36

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-75 Group A: PID Control A-00 Input Terminal for PID Feedback Factory S

Pagina 37 - 2.4.4 Control Terminals

Chapter 5 Parameters|VFD-S Series 5-76 Revision August 2006, SE08, SW V2.61  When this parameter is set to gain =1, PID output is Derivative time.

Pagina 38 - AFM circuit

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-77  This parameter selects the operation of the drive upon a loss of PID f

Pagina 39 - ACI circuit

Chapter 5 Parameters|VFD-S Series 5-78 Revision August 2006, SE08, SW V2.61 the setting frequency of parameters, such as Max. operation frequency, 1s

Pagina 40

Revision August 2006, SE08, SW V2.61 6-1 Chapter 6 Fault Code Information The AC motor drive has a comprehensive fault diagnostic system that inclu

Pagina 41 - Power terminal

Chapter 6 Fault Code Information|VFD-S Series 6-2 Revision August 2006, SE08, SW V2.61 Fault Name Fault Descriptions Corrective Actions Overheating

Pagina 42

Chapter 6 Fault Code Information|VFD-S Series Revision August 2006, SE08, SW V2.61 6-3 Fault Name Fault Descriptions Corrective Actions Over-curre

Pagina 43

Chapter 6 Fault Code Information|VFD-S Series 6-4 Revision August 2006, SE08, SW V2.61 Fault Name Fault Descriptions Corrective Actions Communicati

Pagina 44

Revision August 2006, SE08, SW V2.61 7-1 Chapter 7 Troubleshooting 7.1 Over Current (OC) ocAocdOC Over-current during accelerationOv

Pagina 45

Chapter 7 Troubleshooting |VFD-S Series 7-2 Revision August 2006, SE08, SW V2.61 7.2 Ground Fault GFFGround faultNoYesIs output circuit(cable or m

Pagina 46

Revision August 2006, SE08, SW V2.61 2-1 Chapter 2 Installation and Wiring 2.1 Ambient Conditions Install the AC motor drive in an environment with

Pagina 47

Chapter 7 Troubleshooting |VFD-S Series Revision August 2006, SE08, SW V2.61 7-3 7.4 Low Voltage (Lv) Low voltageIs input power correct? Or power c

Pagina 48 - Chapter 3 Start Up

Chapter 7 Troubleshooting |VFD-S Series 7-4 Revision August 2006, SE08, SW V2.61 7.5 Over Heat (OH) AC motor drive overheatsHeat sink overheatsChec

Pagina 49 - 3.3 Trial Run

Chapter 7 Troubleshooting |VFD-S Series Revision August 2006, SE08, SW V2.61 7-5 7.7 Keypad Display is Abnormal Abnormal display or no displayCycle

Pagina 50

Chapter 7 Troubleshooting |VFD-S Series 7-6 Revision August 2006, SE08, SW V2.61 7.9 Motor cannot Run Motor cannot run Check PU01 for normal

Pagina 51

Chapter 7 Troubleshooting |VFD-S Series Revision August 2006, SE08, SW V2.61 7-7 7.10 Motor Speed cannot be Changed Motor can run butcannot c

Pagina 52

Chapter 7 Troubleshooting |VFD-S Series 7-8 Revision August 2006, SE08, SW V2.61 7.11 Motor Stalls during Acceleration Motor stalls during accelerat

Pagina 53

Chapter 7 Troubleshooting |VFD-S Series Revision August 2006, SE08, SW V2.61 7-9 7.13 Electromagnetic/Induction Noise Many sources of noise surround

Pagina 54 - Setting parameters

Chapter 7 Troubleshooting |VFD-S Series 7-10 Revision August 2006, SE08, SW V2.61 4. Store within a relative humidity range of 0% to 90% and non-co

Pagina 55

Revision August 2006, SE08, SW V2.61 8-1 Chapter 8 Maintenance and Inspections Modern AC motor drives are based on solid-state electronics technolo

Pagina 56 - Chapter 5 Parameters

Chapter 8 Maintenance and Inspections|VFD-S Series 8-2 Revision August 2006, SE08, SW V2.61 Periodical Maintenance  Ambient environment Maintenance

Pagina 57

Chapter 2 Installation and Wiring|VFD-S Series 2-2 Revision August 2006, SE08, SW V2.615. When installing multiple AC motor drives in the same cabi

Pagina 58

Chapter 8 Maintenance and Inspections|VFD-S Series Revision August 2006, SE08, SW V2.61 8-3 Maintenance Period Check Items Methods and Criterion Dai

Pagina 59

Chapter 8 Maintenance and Inspections|VFD-S Series 8-4 Revision August 2006, SE08, SW V2.61  DC capacity of main circuit Maintenance Period Check I

Pagina 60

Chapter 8 Maintenance and Inspections|VFD-S Series Revision August 2006, SE08, SW V2.61 8-5  Printed circuit board and connector of main circuit Ma

Pagina 61

Chapter 8 Maintenance and Inspections|VFD-S Series 8-6 Revision August 2006, SE08, SW V2.61 This page intentionally left blank

Pagina 62

Revision August 2006, SE08, SW V2.61 Appendix A Specifications Voltage Class 115V Class 230V Class 460V Class Model Number VFD-XXXS 002 004

Pagina 63

Appendix A Specifications|VFD-S Series A-2 Revision August 2006, SE08, SW V2.61 Installation Location Altitude 1,000 m or below, keep from corrosi

Pagina 64

Revision August 2006, SE08, SW V2.61 Appendix B Accessories B.1 All Brake Resistors & Brake Units Used in AC Motor Drives Note: Please only use

Pagina 65

Appendix B Accessories|VFD-S Series B-2 Revision August 2006, SE08, SW V2.61 installation and operation. B.1.1 Dimensions and Weights for Brake resi

Pagina 66

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-3 B.2 EMI Filters The DELTA VFD-S Series 0.25-3HP, 115V, 230V, 460V AC dr

Pagina 67

Appendix B Accessories|VFD-S Series B-4 Revision August 2006, SE08, SW V2.61 1. Use the cable with shielding (double shielding is the best). 2. T

Pagina 68

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-32.3 Dimensions (Dimensions are in millimeter and [inch]) Frame

Pagina 69

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-5 The length of motor cable When motor is driven by an AC motor drive of

Pagina 70

Appendix B Accessories|VFD-S Series B-6 Revision August 2006, SE08, SW V2.61  If the length is too long, the stray capacitance between cables will

Pagina 71

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-7 Order P/N: RF022S21BA 27(1.06)50(1.97)228(8.98)15(0.59)24(0.94)100(3.94

Pagina 72

Appendix B Accessories|VFD-S Series B-8 Revision August 2006, SE08, SW V2.61 Order P/N: 12DKT1W3S POWER-IN Order P/N: 08TDT1W4S

Pagina 73

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-9 Order P/N: 22DRT1W3S POWER-IN Order P/N: 35DRT1W3C POWER-IN

Pagina 74 - Unit: 1

Appendix B Accessories|VFD-S Series B-10 Revision August 2006, SE08, SW V2.61 B.3 AC Reactor B.3.1 AC Input Reactor Recommended Value 230V, 50/60Hz,

Pagina 75

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-11 460V, 50/60Hz, 3-Phase Inductance (mH) kW HP Fundamental Amps Max. co

Pagina 76

Appendix B Accessories|VFD-S Series B-12 Revision August 2006, SE08, SW V2.61 may be damaged when over current occurs during operation.

Pagina 77 - Unit: 0.1

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-13 Correct wiring M1M2MnreactorAC motor driveAC motor driveAC motor drive

Pagina 78

Appendix B Accessories|VFD-S Series B-14 Revision August 2006, SE08, SW V2.61 Application 3 Question Used to improve the input power factor, to re

Pagina 79

Chapter 2 Installation and Wiring|VFD-S Series 2-4 Revision August 2006, SE08, SW V2.61Frame S1: VFD002S11B, VFD002S21B 11.1[0.44]5.0 [0.20]74 .0 [

Pagina 80

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-15 B.4 DC Choke Recommended Values 230V DC Choke Input voltage kW HP

Pagina 81

Appendix B Accessories|VFD-S Series B-16 Revision August 2006, SE08, SW V2.61 B.5 Zero Phase Reactor (RF220X00A) Dimensions are in millimeter and (

Pagina 82 - Current signal input(4-20mA)

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-17 B.6 Din Rail-DR01 (Dimensions are in millimeter) Models Screw SizeV

Pagina 83

Appendix B Accessories|VFD-S Series B-18 Revision August 2006, SE08, SW V2.61 B.7 Remote Controller RC-01 (Dimensions are in millimeter) AFMGND +10

Pagina 84

Appendix B Accessories|VFD-S Series Revision August 2006, SE08, SW V2.61 B-19 B.8 Conduit Bracket (BK-S) (Dimensions are in millimeter) 22.0(0.87)2

Pagina 85

Appendix B Accessories|VFD-S Series B-20 Revision August 2006, SE08, SW V2.61 B.9 Non-fuse Circuit Breaker Chart Per UL 508C, paragraph 45.8.4, part

Pagina 86 - Analog Frequency Meter

Revision August 2006, SE08, SW V2.61 Appendix C How to Select the Right AC Motor Drive The choice of the right AC motor drive for the application is

Pagina 87

Appendix D CE|VFD-S Series C-2 Revision August 2006, SE08, SW V2.61 C.1 Capacity Formulas 1. When one AC motor drive operates one motor The starting

Pagina 88

Error! Reference source not found. Error! Reference source not found.|VFD-S Series Revision August 2006, SE08, SW V2.61 C-3 2.3 When it is running

Pagina 89

Appendix D CE|VFD-S Series C-4 Revision August 2006, SE08, SW V2.61 C.2 General Precautions Selection Note A. When the AC Motor Drive is connected

Pagina 90

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-5Frame S1: VFD004S11A, VFD004S21A, VFD004S23A 5.0 [0.20]3.0[0.

Pagina 91

Error! Reference source not found. Error! Reference source not found.|VFD-S Series Revision August 2006, SE08, SW V2.61 C-5 D. If the stall preve

Pagina 92 - Potentiometer Scale

Appendix D CE|VFD-S Series C-6 Revision August 2006, SE08, SW V2.61 E. If 100% continuous torque is required at low speed, it may be necessary to u

Pagina 93 - key to switch

Error! Reference source not found. Error! Reference source not found.|VFD-S Series Revision August 2006, SE08, SW V2.61 C-7 D. Gear reduction mot

Pagina 94

Appendix D CE|VFD-S Series C-8 Revision August 2006, SE08, SW V2.61 AC motor drive Motor 18015514010080553803206012060 secondsBase freq.: 60HzV/F

Pagina 95

Revision August 2006, SE08, SW V2.61 Appendix D CE DELTA ELECTRONICS, INC. EC Declaration of Conformity According to the Low Voltage Directive 73/2

Pagina 96

Appendix D CE|VFD-S Series D-2 Revision August 2006, SE08, SW V2.61 DELTA ELECTRONICS, INC. EC Declaration of Conformity According to the Low Volt

Pagina 98

Chapter 2 Installation and Wiring|VFD-S Series 2-6 Revision August 2006, SE08, SW V2.61Frame S1: VFD004S11B, VFD004S21B 3.0[0.12]5.0 [0.20]102.0 [4

Pagina 99

Preface Thank you for choosing DELTA’s high-performance VFD-S Series. The VFD-S Series is manufactured with high-quality components and materials and

Pagina 100 - Reset counter

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-7Frame S1: VFD007S21A, VFD007S23A 85.0 [3 .3 5]132.2[5.21]74.0

Pagina 101 - RUN/STOP

Chapter 2 Installation and Wiring|VFD-S Series 2-8 Revision August 2006, SE08, SW V2.61Frame S1: VFD007S21B 11.1[0.44]3.0[0.12]5.0 [0.20]2.8 [0.11]

Pagina 102

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-9Frame S1: VFD004S43A, VFD004S43E, VFD007S43A, VFD007S43E 11.1

Pagina 103

Chapter 2 Installation and Wiring|VFD-S Series 2-10 Revision August 2006, SE08, SW V2.61Frame S1: VFD004S43B, VFD007S43B 5.0 [0.20]11.1[0.44]67 .8

Pagina 104

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-11Frame S1: VFD002S21E, VFD004S21E, VFD007S21E, VFD015S23D 74.

Pagina 105

Chapter 2 Installation and Wiring|VFD-S Series 2-12 Revision August 2006, SE08, SW V2.61Frame S2: VFD007S11A 86 .5 [3 .4 1]100.0 [3.94]129.0 [5.08]

Pagina 106

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-13Frame S2: VFD007S11B 86.5 [3 .4 1]100.0 [3.94]73.0 [2 .8 8]9

Pagina 107

Chapter 2 Installation and Wiring|VFD-S Series 2-14 Revision August 2006, SE08, SW V2.61Frame S2: VFD015S21D, VFD015S21E, VFD015S43D, VFD015S43E, VF

Pagina 108

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-15Frame S2: VFD015S21U, VFD015S43U, VFD022S21U, VFD022S43U 86.

Pagina 109

Chapter 2 Installation and Wiring|VFD-S Series 2-16 Revision August 2006, SE08, SW V2.612.4 Wiring After removing the front cover, check if the powe

Pagina 110

WARNING! 1. DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor drive is easily damaged by high-pressure. 2. Th

Pagina 111

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-172.4.1 Basic Wiring  Make sure that power is only applied to

Pagina 112

Chapter 2 Installation and Wiring|VFD-S Series 2-18 Revision August 2006, SE08, SW V2.61For VFDXXXSXXA/B/D/U 4.7k47KGrounding resistanceless than 1

Pagina 113 - Output Frequency

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-19For VFDXXXSXXE NPN (sink mode) B2U/T1V/T2W/T3IM3~NOTE: Do no

Pagina 114

Chapter 2 Installation and Wiring|VFD-S Series 2-20 Revision August 2006, SE08, SW V2.61For VFDXXXSXXE PNP (source mode) B2U/T1V/T2W/T3IM3~NOTE: Do

Pagina 115

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-212.4.2 External Wiring MotorOutput AC Line ReactorPower Supply

Pagina 116

Chapter 2 Installation and Wiring|VFD-S Series 2-22 Revision August 2006, SE08, SW V2.612.4.3 Main Terminals Connections Terminal Symbol Explanatio

Pagina 117 - Computer

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-23 DO NOT connect phase-compensation capacitors or surge absor

Pagina 118

Chapter 2 Installation and Wiring|VFD-S Series 2-24 Revision August 2006, SE08, SW V2.612.4.4 Control Terminals Control Terminal Wiring (Factory Set

Pagina 119 - ( 7.E.1)

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-25Terminal Symbol Terminal Function Factory Settings (NPN mode)

Pagina 120

Chapter 2 Installation and Wiring|VFD-S Series 2-26 Revision August 2006, SE08, SW V2.61Terminal Symbol Terminal Function Factory Settings (NPN mode

Pagina 121

Table of Contents Preface ...i Table of C

Pagina 122

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-27Digital outputs (MO1, MCM)  Make sure to connect the digital

Pagina 123

Chapter 2 Installation and Wiring|VFD-S Series 2-28 Revision August 2006, SE08, SW V2.612.4.5 Main Circuit Terminals VFD002S11A/11B, VFD004S11A/11B

Pagina 124

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-29VFD002S21B/23A, VFD004S21B/23A/43A/43B/43E, VFD007S21B/23A/43

Pagina 125

Chapter 2 Installation and Wiring|VFD-S Series 2-30 Revision August 2006, SE08, SW V2.61VFD002S21A/E, VFD004S21A/E, VFD007S21A/E DC ReactorBrakingR

Pagina 126

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-31VFD007S11A/B AC Input Line TerminalPower terminal MotorC

Pagina 127

Chapter 2 Installation and Wiring|VFD-S Series 2-32 Revision August 2006, SE08, SW V2.61VFD015S21U/43D/43E/43U, VFD022S21U/23D/43D/43E/43U AC Input

Pagina 128

Chapter 2 Installation and Wiring|VFD-S Series Revision August 2006, SE08, SW V2.61 2-33VFD015S21D/E, VFD022S21D/E BrakingResistorDC ReactorGroundPow

Pagina 129

Chapter 2 Installation and Wiring|VFD-S Series 2-34 Revision August 2006, SE08, SW V2.61 This page intentionally left blank

Pagina 130

Revision August 2006, SE08, SW V2.61 3-1 Chapter 3 Start Up 3.1 Preparations before Start-up Carefully check the following items before proceeding.

Pagina 131

Chapter 3 Start Up| VFD-S Series 3-2 Revision August 2006, SE08, SW V2.613.2 Operation Method Refer to 4.2 How to operate the digital keypad and cha

Pagina 132 - Sleep Function

Chapter 3 Start Up...3-1 3.1 Preparations before Start-up...

Pagina 133 - Per output

Chapter 3 Start Up| VFD-S Series Revision August 2006, SE08, SW V2.61 3-3NOTE 1. Stop running immediately if any fault occurs and refer to the troub

Pagina 134 - Fault Code Information

Chapter 3 Start Up| VFD-S Series 3-4 Revision August 2006, SE08, SW V2.61This page intentionally left blank

Pagina 135

Revision August 2006, SE08, SW V2.61 4-1 Chapter 4 Digital Keypad Operation 4.1 Description of the Digital Keypad RUNFWDREVSTOPMIN. MAX.RUNSTOP/RESE

Pagina 136

Chapter 4 Digital Keypad Operation|VFD-S Series 4-2 Revision August 2006, SE08, SW V2.61Display Message Descriptions The internal PLC process step

Pagina 137 - 6.2 Reset

Chapter 4 Digital Keypad Operation|VFD-S Series Revision August 2006, SE08, SW V2.61 4-3 4.4 How to Operate the Digital Keypad STARTTo shift dataSet

Pagina 138 - Chapter 7 Troubleshooting

Chapter 4 Digital Keypad Operation|VFD-S Series 4-4 Revision August 2006, SE08, SW V2.61This page intentionally left blank

Pagina 139 - 7.3 Over Voltage (OV)

Revision August 2006, SE08, SW V2.61 5-1 Chapter 5 Parameters The VFD-S parameters are divided into 11 groups by property for easy setting. In most

Pagina 140 - 7.4 Low Voltage (Lv)

Chapter 5 Parameters|VFD-S Series 5-2 Revision August 2006, SE08, SW V2.61 5.1 Summary of Parameter Settings : The parameter can be set during opera

Pagina 141 - 7.6 Overload

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-3 Pr. Explanation Settings Factory SettingNOTE 460V series: d4.0V to d51

Pagina 142 - 7.8 Phase Loss (PHL)

Chapter 5 Parameters|VFD-S Series 5-4 Revision August 2006, SE08, SW V2.61 Pr. Explanation Settings Factory SettingNOTE2-00 Source of Master Frequen

Pagina 143 - 7.9 Motor cannot Run

7.9 Motor cannot Run ... 7-6 7.10 Motor Speed canno

Pagina 144

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-5 Pr. Explanation Settings Factory SettingNOTE3-00 Analog Output Signal d0

Pagina 145

Chapter 5 Parameters|VFD-S Series 5-6 Revision August 2006, SE08, SW V2.61 Pr. Explanation Settings Factory SettingNOTE4-05 Multi-Function Input Ter

Pagina 146 - 7.14 Environmental Condition

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-7 Pr. Explanation Settings Factory SettingNOTE5-02 3rd Step Speed Freq. d

Pagina 147

Chapter 5 Parameters|VFD-S Series 5-8 Revision August 2006, SE08, SW V2.61 Pr. Explanation Settings Factory SettingNOTE6-05 Over-Torque Detection T

Pagina 148

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-9 Group 7 Motor Parameters Pr. Explanation Settings Factory SettingNOTE7-

Pagina 149

Chapter 5 Parameters|VFD-S Series 5-10 Revision August 2006, SE08, SW V2.61 Pr. Explanation Settings Factory SettingNOTE9-00 Communication Address

Pagina 150

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-11 Pr. Explanation Settings Factory SettingNOTEA-07 PID Output Freq. Limit

Pagina 151

Chapter 5 Parameters|VFD-S Series 5-12 Revision August 2006, SE08, SW V2.61 5.2 Parameter Settings for Applications  Speed Search Applications Purp

Pagina 152

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-13  Two-wire/three-wire Applications Purpose Functions Related Parameters

Pagina 153

Chapter 5 Parameters|VFD-S Series 5-14 Revision August 2006, SE08, SW V2.61  Over-torque Setting Applications Purpose Functions Related Parameters

Pagina 154 - Appendix A Specifications

Appendix C How to Select the Right AC Motor Drive...C-1 C.1 Capacity Formulas ...

Pagina 155

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-15  Output Signal during Running Applications Purpose Functions Related P

Pagina 156 - Appendix B Accessories

Chapter 5 Parameters|VFD-S Series 5-16 Revision August 2006, SE08, SW V2.61  Output Signal when Frequency Attained Applications Purpose Functions

Pagina 157

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-17 5.3 Description of Parameter Settings Group 0: User Parameters

Pagina 158 - B.2 EMI Filters

Chapter 5 Parameters|VFD-S Series 5-18 Revision August 2006, SE08, SW V2.61 d4 Display forward/reverse command (Frd/rEv) 0-04 Content of Mul

Pagina 159

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-19 0-07 Password Input Unit: 1 Settings d0 to d999 Factory Setting: d0

Pagina 160

Chapter 5 Parameters|VFD-S Series 5-20 Revision August 2006, SE08, SW V2.61 3 chances to enter the correctpassword.1st time displays "d 1"

Pagina 161 - B.2.1 Dimensions

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-21 bit 5 bit4 Bit 3 bit 1 Setting for Pr. 0-09 0 0 0 1 2 0 8 (factory

Pagina 162 - Order P/N: RF022S21BA

Chapter 5 Parameters|VFD-S Series 5-22 Revision August 2006, SE08, SW V2.61 Group 1: Basic Parameters 1-00 Maximum Output Frequency (Fmax) Unit: 0.1

Pagina 163 - POWER-IN

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-23  This parameter sets the Mid-Point Voltage of any V/f curve. With this

Pagina 164

Chapter 5 Parameters|VFD-S Series 5-24 Revision August 2006, SE08, SW V2.61  If the Upper Limit of Output Frequency is 50Hz and the Maximum Output

Pagina 165 - B.3 AC Reactor

Revision August 2006, SE08, SW V2.61 1-1 Chapter 1 Introduction 1.1 Receiving and Inspection This VFD-S AC motor drive has gone through rigorous qua

Pagina 166 - 1/2 2 3 20 32

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-25  The JOG function can be selected using Multi-function Input terminals

Pagina 167

Chapter 5 Parameters|VFD-S Series 5-26 Revision August 2006, SE08, SW V2.61 1-16 Acceleration S-Curve 1-17 Deceleration S-Curve Settings d0 t

Pagina 168

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-27 Group 2: Operation Method Parameters 2-00 Source of Master Frequency Com

Pagina 169

Chapter 5 Parameters|VFD-S Series 5-28 Revision August 2006, SE08, SW V2.61 2-01 Source of Operation Command Factory Setting: d0 Settings d

Pagina 170

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-29 RUNSTOPRUNSTOPFrequencyFrequencyTimeTimeoutputfrequencyoutputfrequencymot

Pagina 171 - Zero Phase Reactor

Chapter 5 Parameters|VFD-S Series 5-30 Revision August 2006, SE08, SW V2.61 2-05 Loss of ACI Signal (4-20mA) Factory Setting: d0 Settings d

Pagina 172 - B.6 Din Rail-DR01

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-31 Group 3: Output Function Parameters 3-00 Analog Output Signal (AFM)

Pagina 173 - B.7 Remote Controller RC-01

Chapter 5 Parameters|VFD-S Series 5-32 Revision August 2006, SE08, SW V2.61 3-02 Desired Frequency Attained Unit: 0.1 Settings d1.0 to d400 Hz

Pagina 174 - B.8 Conduit Bracket (BK-S)

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-33 Preliminary Counter Value Attained Output(Pr. 3-04=d3)(Pr. 3-05 to Pr. 3-

Pagina 175 - Fuse Specification Chart

Chapter 5 Parameters|VFD-S Series 5-34 Revision August 2006, SE08, SW V2.61 Setting Function Description d10 PLC Program Running the output will

Pagina 176

Chapter 1 Introduction|VFD-S Series 1-2 Revision August 2006, SE08, SW V2.611.1.3 Series Number Explanation 0160T007S23AProduction numberProduction

Pagina 177 - C.1 Capacity Formulas

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-35 Group 4: Input Function Parameters 4-00  Potentiometer Bias Frequency

Pagina 178 - )(_____103

Chapter 5 Parameters|VFD-S Series 5-36 Revision August 2006, SE08, SW V2.61 Example 3: The example also shows the popular method. The whole scale o

Pagina 179 - C.2 General Precautions

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-37 Example 6: In this example, a negative bias is used to provide a noise

Pagina 180 - Load duty-cycle

Chapter 5 Parameters|VFD-S Series 5-38 Revision August 2006, SE08, SW V2.61 Hz 0V4mA10V20mA30060Potentiometer ScaleMax.OutputFreq.60HzPr.1-000Hz 0V4

Pagina 181 - Appendix D CE

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-39 Explanations: d0 Parameter Disable: Enter value (d0) to disable any Multi

Pagina 182 - Motor torque

Chapter 5 Parameters|VFD-S Series 5-40 Revision August 2006, SE08, SW V2.61 NOTE When value d3 is selected for Pr. 4-04, this will over ride any valu

Pagina 183 - AC motor drive Motor

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-41 GNDD7 Multi-step 1D8 Multi-step 2D9 Multi-step 3Mx "Close": Ope

Pagina 184 - Appendix D CE

Chapter 5 Parameters|VFD-S Series 5-42 Revision August 2006, SE08, SW V2.61 FrequencyMaster FrequencyAccelerationinhibitAcceleration inhibitActual op

Pagina 185 - EC Declaration of Conformity

Chapter 5 Parameters|VFD-S Series Revision August 2006, SE08, SW V2.61 5-43 GNDB.B.(N.O.)setting by d13B.B.(N.C.)setting by d14Mx "Close":

Pagina 186

Chapter 5 Parameters|VFD-S Series 5-44 Revision August 2006, SE08, SW V2.61 GNDsetting by d17setting by d18Mx "Close": Run PLC.Mx "Clo