Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
45
Example 2:
In this example with the potentiometer set to 0V the Output Frequency is 10 Hz.
The mid-point of the potentiometer becomes 40 Hz. Once the Maximum Output
Frequency is reached any further increase of the potentiometer will not increase
output frequency.
Pr.4-02=100%-- Pot. Freq. Gain
Example 3:
The example also shows the popular method. The whole scale of the
potentiometer can be used as desired. In addition to signals of 0 to 10V and 4 to
20mA, the popular voltage signals also include signals of 0 to 5V, 20 to 4mA or
that under 10V. Regarding the setting, please refer to the following examples.
Pr.4-02=83%-- Pot. Freq. Gain