Chapt er 6 Troubles h o o ting
6-3
If an HMI can not communicate with a controller, users can refer to the following table for more
information about the error code shown on the screen.
code
Communication error
message
Reason Troubleshooting
0x02
Unknown Noise interference
Strengthen the
equipment’s immunity to
noise, and use shielded
cables.
0x03
NoResponse
The wiring, the PLC station
number, and the values of the
communication parameters
(baudrate, parity bit, data bits,
stop bit) are incorrect.
Please check whether the
related setting is incorrect.
0x05
ControllerCheckSumError
When the HMI checks the PLC
checksum, an error is found.
Please check whether the
PLC checksum is
incorrect. Users usually
have to use PLC software.
0x06
CommandError
The command sent to the PLC
is incorrect.
Please check whether the
command sent by HMI is
supported by the PLC.
0x07
AddressError
The PLC address from which
data is read, or the PLC
address into which data is
written is incorrect.
Please check whether the
PLC address set by the
HMI is not supported by
the PLC, or data can not
be written into this
address.
0x08
ValueError
The data written into the PLC is
incorrect.
Pleas make sure of the
values which can be
accepted by the PLC.
0x0A
NoCTS
The CTS pin in HMI does not
receive the RTS signal from the
PLC.
Please check whether the
CTS pin in the HMI is
connected to the RTS pin
in the PLC, or PLC sends
the RTS signal.
0x0E
HMIStationNumberError
The HMI station number is
incorrect.
Please check whether the
station number of the HMI
exceeds the legal range,
or is the same as the
station number of another
station.
0x0F
PLCStationNumberError
The PLC station number is
incorrect.
Please check whether the
station number of the PLC
exceeds the legal range,
or is the same as the
station number of another
station.
0x10
UARTCommunicateFail
The bottom communication of
the HMI is incorrect. The COM
port is not opened correctly, or
the HIM works so hard that the
COM port can not function
normally.
Please check whether the
COM port used can
function normally, or
simply the operation of the
HMI, e.g. delete the
instructions ALARM and
MACRO.
If the program in an HMI is destroyed or lost, please connect the HMI to a computer, and download
the program again. Please refer to chapter 2 for more information.