Train ing Kit O peratio n Manua l
4-4
The HMI displays the devices which are involved in data exchange.
HMI
Data source
C0
Device in which data read from
DVP28SV2 is stored
D6039
Device in which data read from
DVP12SA2 is stored
D1484
Device in which data read from
DVP20SX2 is stored
D104
1. Data exchange table
The master station DVP12SE exchanges data with DVP28SV2 through CANopen.
Master station/Slave station Master Direction
Slave
PLC DVP12SE
DVP28SV2
Writing data into DVP28SV2 D6289 D6039
Reading data from DVP28SV2
D6039 D6289
The master station DVP12SE exchanges data with DVP12SA2 through RS-485.
Master station/Slave station Master Direction
Slave
PLC DVP12SE
DVP12SA2
Writing data into DVP12SA2 D1498 D202
Reading data from 12SA2 D1484 D104
The master station DVP12SE exchanges data with DVP20SX2 through Ethernet.
Master station/Slave station Master Direction
Slave
PLC DVP12SE
DVP20SX2
Writing data into DVP20SX2 D202 D102
Reading data from DVP20SX2
D104 D204
2. Control program
The RS-485 communication setting of the master station DVP12SE is shown below.