Delta Electronics Ethernet Communication Module DVPEN01-SL Manual de usuario Pagina 8

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 54
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 7
Ethernet Communication Module DVPEN01-SL
DVP-PLC Application Manual
6
Connect DVPEN01-SL to the Network
Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX
function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL.
Network connection between the PC and DVPEN01-SL:
4 Control Register (CR)
4.1 Control Registers in DVPEN01-SL
CR#
HW LW
Attribute Content Explanation
#0 R Model name
Set up by the system; read only. Model code of DVPEN01-SL
= H’4050
#1 R Firmware version Displaying the current firmware version in hex.
#2 R Communication mode b0: Modbus TCP mode; b1: data exchange mode
#3 W E-Mail Event 1 trigger Set up whether to send E-Mail 1
#4 W E-Mail Event 2 trigger Set up whether to send E-Mail 2
#5 W E-Mail Event 3 trigger Set up whether to send E-Mail 3
#6 W E-Mail Event 4 trigger Set up whether to send E-Mail 4
Ethernet
PC Maste
r
DVP28SV
LAN
RS-232
RS-232
LINK
100M
DVPEN01
POWER
DVP28SV
DVPEN01
DVP28SV
LAN
RS-232
RS-232
LINK
100M
DVPEN01
POWER
DVP28SV
DVPEN01