1 TPEditor Operation
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
1-36
Figure 1-64
Step 3. It is used to set write-in PLC Device Name, i.e. T, C, D or the Device Name, i.e. @V of TP05/08. The
Device Number is shown in decimal format and the users could click
to select the necessary
Device Name. If the connected controller is AC motor drive (Inverter), it does not need to check the
Device Name. The symbol $ will show after the Device Name to represent the absolute address of AC
motor drive. What the users need to do is to input absolute address in the field of Device Number. For
example, enter the register D10, timer T1 and the absolute address of AC motor drive $2003 to read
the output frequency. The communication address is used to determine which PLC or AC motor drive
will be communicated with, i.e. the communication address of the connected PLC or AC motor drive.
The users also could select COM1 (RS-232) or COM2 (RS-485/RS-422) for the communication port
that used to connect to the monitored equipment. After completing the settings, click OK button, and
return to Numeric/ASCII Display Setting tab (Figure 1-63).
Step 4. In the Numeric/ASDII Display Setting tab, the users can enter Refer Device, select Value Type and
Length, choose Integer and Decimal Number, determine Frame Setting Font Setting and Alignment,
and decide if Leading Zeros option is enabled or not.
Step 5. Value Type could be Unsigned, Signed, Hex, BCD, ASCII, Binary and Float these selections. Value
Length could be either 16 bits or 32 bits. Alignment option is used to align the display value to be left,
right or middle.
Step 6. Integer Number and Decimal Number are used to set the display value and its decimal places. For
example, suppose that the value of Timer T0 is K500 and its actual value is 50 seconds. If the Integer
Number is set to 3, the display value will be 500. If the Decimal Number is set to 1 as well, the display
value will be 050.0, i.e. the actual timer value.
Step 7. Frame Setting could be No Frame, Single Frame, Double Frame, Thick Frame, Dotted Line Frame or
Dot Frame for selections. As for the Font Setting, the users could choose 5x8, 8x8, 8x12 or 8x16.
Step 8. If the Leading Zeros option is enabled, it indicates that the users want to fill 0 before the display value.
For example, suppose that the entered value is 324836, if Integer Number is set to 6 and Decimal
Number is set to 2, when the Leading Zeros option is not enabled, the display value will be 3248.36.
But, under the same conditions, when the Leading Zeros option is enabled, the display value will be
003248.36.