Delta Electronics VFD-L Series Manual de usuario Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
10
Parameters Functions Settings
Factory
setting
4-06 Multi-function input 7
terminal 3(M3)
(d 0, d 4d 20)
14: increase master freq.
15: decrease master freq.
16: run PLC program
17: pause PLC
18: counter trigger signal
19: counter reset
20: select ACI/deselect AVI
Group 5: Multi-step Speed and PLC Parameters
Parameters Functions Settings
Factory
Setting
5-00 1
st
step speed freq. 0.0 ~ 400Hz 0.0
5-01 2
nd
step speed freq. 0.0 ~ 400Hz 0.0
5-02 3
rd
step speed freq. 0.0 ~ 400Hz 0.0
5-03 PLC mode 0: Disable PLC operation
1: Execute one program cycle
2: Continuously execute program cycles
3: Execute one program cycle step by step
(separate by STOP)
4: Continuously execute one program cycle step by
step (separate by STOP)
0
5-04 PLC forward/reverse
motion
0 ~ 15 (0: Forward 1: Reverse) 0
5-05 Time duration step 0 0 ~ 65500 Sec 0
5-06 Time duration step 1 0 ~ 65500 Sec 0
5-07 Time duration step 2 0 ~ 65500 Sec 0
5-08 Time duration step 3 0 ~ 65500 Sec 0
Group 6: Protection Parameters
Parameters Functions Settings
Factory
Setting
6-00
Over-Voltage
Prevention Level
0:disable
350~410V
390
6-01 Over-current
Prevention Level
0: disable
20~200%
170
6-02 Over-torque
detection
0:disable
1:enable during constant speed operation and
continues until the continuous limit is reached.
2:enabled during constant speed operation and
halted after detection.
3:enabled during accel and continues before
continuous output time limit is reached.
4:enabled during accel and halted after over-torque
detection.
0
6-03
Over-torque
detection level
30 ~ 200% 150
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16

Comentarios a estos manuales

Sin comentarios