Chapter 3 Summary of Parameters
Group 0: User Parameters
aThe parameter may be set during operation.
Parameters Functions Settings
Factory
Setting
0-00
Identity code of drive
(Read only)
1: 40W
2: 100W
3: 200W
4: 400W
5: 750W
6: 1.5KW
0-01
Rated current display
(Read only)
40W: 0.4A
100W: 0.8A
200W: 1.6A
400W: 2.5A
750W: 4.2A
1.5K: 7.0A
0-02 Parameter reset 10: Reset Parameters to Factory Setting 0
a
0-03 Start-up display of AC
drive
0: F (Frequency command)
1: H (output frequency)
2: U (user-defined unit)
3: A (output current)
0
a
0-04 User-defined Unit
0: Display User-Defined Unit (u)
1: Display Counter Value (C)
2: Display Process Operation (1=tt)
3: Display DC-BUS voltage (U)
4: Display output voltage (E)
0
a
0-05 User-defined coefficient K
0.1 ~ 160
1.0
0-06 Software version Read only #.#
0-07 Password input 0 ~ 999 0
0-08 Password configuration 0 ~ 999 0
Group 1: Basic Parameters
Parameters Functions Settings
Factory
Setting
1-00 Maximum operation Freq. 50.0 ~ 400Hz 60.0
1-01 Maximum setting Freq. 10.0 ~ 400Hz 60.0
1-02 Maximum output voltage 2.0 ~ 255V 220
1-03 Mid-point freq. 1.0 ~ 400Hz 1.0
1-04 Mid-point voltage 2.0 ~ 255V 12.0
1-05 Minimum output freq. 1.0 ~ 60.0Hz 1.0
1-06 Minimum output voltage 2.0 ~ 255V 12.0
1-07 Upper bound of freq. 1 ~ 110% 100
1-08 Lower bound of freq. 0 ~ 100% 0.0
a
1-09 Accel time 1 (Tacc1) 0.1 ~ 600 Sec 10.0
a
1-10 Decel time 1 (Tdec1) 0.1 ~ 600 Sec 10.0
a
1-11 Accel time 2 0.1 ~ 600 Sec 10.0