12
Parameters Functions Settings
Factory
Setting
8-05
Max. allowable power loss
time
0.3 ~ 5.0 Sec 2.0
8-06 B.B. time for speed search 0.3~5.0 Sec 0.5
8-07
Max. speed search current
level
30~200% 150
8-08 Skip freq. 1 upper bound 0.0~400 Hz 0.0
8-09 Skip freq. 1 lower bound 0.0~400 Hz 0.0
8-10 Skip freq. 2 upper bound 0.0~400 Hz 0.0
8-11 Skip freq. 2 lower bound 0.0~400 Hz 0.0
8-12 Skip freq. 3 upper bound 0.0~400 Hz 0.0
8-13 Skip freq. 3 lower bound 0.0~400 Hz 0.0
8-14 Auto restart after fault 0~10 0
8-15 AVR function 0: AVR function enable
1: AVR function disable
2: AVR function disable when decel
2
8-16 Dynamic braking voltage 350 ~ 450V 380
8-17 DC braking lower bound limit 0.0 ~ 400 Hz 0.0
Group 9: Communication Parameters
Parameters Functions Settings
Factory
Setting
a
9-00 Communication address 1 ~ 247 1
a
9-01 Transmission speed 0: Baud rate 4800
1: Baud rate 9600
2: Baud rate 19200
1
a
9-02 Transmission fault
treatment
0: Warn and continue running
1: Warn and ramp to stop
2: Warn and coasting stop
3: No warn and keep running
0
a
9-03
Modbus communication
watchdog timer
0: Disable
1~20: 1 ~ 20 Sec
0
ASCII
mode
0: 7,N,2
1: 7,E,1
2: 7,O,1
3: 8,N,2
4: 8,E,1
5: 8,O,1
a
9-04 Communication
protocol
RTU
mode
6: 8,N,2
7: 8,E,1
8: 8,O,1
0