Ethernet Communication Module DVPEN01-SL
CR#27: Function code for a data exchange mode
Explanations:
0: Using the function code “0x17” for the reading of data and the writing of data
1: Using the function code
“0x03” for the reading of data; using the function code “0x06” for the writing of a single piece
of data; using the function code “
0x10” for the writing of multiple pieces of data
CR#28: Destination slave ID
Explanations:
When you set the Salve ID (i.e. K1~K255) for data exchange, DVPEN01-SL will automatically search for the
corresponding IP address from the slave IP address list. For example, if the ID is set as “0”, the value in CR#25 and
#26 will be regarded as the destination IP address.
CR#29~48: Data transmission buffer
Explanations:
Storing the data to be transmitted to the remote MPU.
CR#49~68: Data receiving buffer
Explanations:
Storing the data received from the remote MPU.
CR#81: Read address for data exchange
Explanations:
Setting manually the MODBUS address of the register for Slave data exchange
Only register address is allowed (e.g. D0=H’1000).
CR#82: Read length for data exchange
Explanations:
The number of receiving registers (K1~K100) in data exchange.
CR#83: Read length for data exchange
Explanations:
Setting the MODBUS address of the register for Master data exchange
CR#84: Written-in address for data exchange
Explanations:
Setting manually the MODBUS address of the register for Slave data exchange