5.12 Returning to Default Settings
If you need to clear all the settings after many modifications on the settings and return the settings to default ones,
select the Factory Setting checkbox.
Returning to default settings
Select the Factory Setting checkbox, and click on Yes.
Note:
If you set DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked
or not. It takes approximately 10 seconds to return to default setting, so DO NOT
switch off the power within the
10 seconds.
6 Application Examples
6.1 Setting an IP Address and Communication through WPLSoft
Application Setting the network parameters of DVPEN01-SL directly on the PC.
Network
environment
(1) IP address of the PC executing WPLSoft: 192.168.0.3
(2) Subnet mask: 255.255.255.0; Gateway: 192.168.0.1
(3) IP address of DVPEN01-SL: 192.168.0.4
(4) Connect the PC and DVPEN01-SL by RJ-45 cable.
Note: Both PC and DVPEN01-SL have to adopt a static IP address.
1. The connection
PC
DVP-PLC
DVPEN01
DVP-PLC Operation Manual
34