Ethernet Communication Module DVPEN01-SL
detect by the previou
s setting that No. 1 IP address is “192.168.0.4".
Write the data in RTC into CR#29~CR#35.
Write “1” into CR#13 to start the data exchange.
CR#14=2 refers to successful exchange. CR#14=3 refers to failed exchange.
5. Compile the ladder diagram for PLC_A and download it to PLC_A.
END
M1013
K7D0K49K100FROM
Explanations:
The received data are stored in CR#49~CR#55.
The data received every one second are written into D0~D6.
6.9 Application of Data Exchange (2)
Firmware version 2.0 and above support this function.
Application
Select Always Enable in the Enable Condition drop-down list box. Enable a timer and write the timer
values into D0~D99. Continuosly write the present values in D0~D99 of PLC_A into D0~D99 of
PLC_B, and write the values in D0~D99 of PLC-B into D200~D299 of PLC_A.
Network
environment
(1) Adopt a static IP address.
(2) IP address of PLC_A: 192.168.1.99
(3) IP address of PLC_B: 192.168.1.97
(4) Update from PLC_A to PLC_B and PLC_B to PLC_A.
1. See 6.1 for how to set the communication.
2. Open the setup page of PLC_A and switch to the Data Exchange page.
DVP-PLC Operation Manual
50