Ethernet Communication Module DVPEN01-SL
CR#94: Enabling the setting of an IP address
Explanations:
If the value in CR#94 is 1, the setting of an IP address will be enabled. After the setting is complete, the value in CR#94
will automatically become 0.
CR#95: Status of setting an IP adress
Explanations:
The control register is used to show the status of setting an IP address. If the value in CR#95 is 0, the setting of an IP
address is successful. If the value in CR#95 is 1, the setting of an IP address is being executed.
Sending MODBUS TCP Instruction
CR#111: 8-bit processing mode
Explanations:
Setting the MODBUS TCP transmission mode
When the CR value is set as “0”16-bit mode; when the CR value is set as “1”8-bit mode.
CR#112: MODBUS client Keepalive time-out
Explanations:
CR#112 is the TCP Keepalive timeout for MODBUS TCP connection. (Unit: Second)
Default: 30s
If the connection idle time becomes longer than the keep-alive time-out, DVPEN01-SL will cut off the idle connection.
CR#114: MODBUS TCP timeout
Explanations:
Setting the communication time-out (in ms) for MODBUS TCP mode
CR#115: MODBUS TCP trigger
Explanations:
When the CR value is set as “1”, MODBUS TCP will be triggered. After the data transmission is completed in MODBUS
TCP mode, the CR value will automatically be reset to “0”. Please trigger by differential instructions.
CR#116: MODBUS TCP status
Explanations:
Displaying the current communication status of MODBUS TCP mode
When the CR value is set as”0”the data have not yet been received; when the CR value is set as “1”the data
exchange is in progress; when the CR value is set as “2”the data exchange is successful; when the CR value is set
as “3”the data exchange fails.