Ethernet Communication Module DVPEN01-SL
6.6 Setting a Static ARP Table
Application Setting a static ARP table
Network
environment
(1) MAC address of equipment 192.168.1.6 is 00:18:23:10:00:35
(2) MAC address of equipment 192.168.1.1 is 00:18:23:10:00:04
1. See 6.1 for the connection and how to set the communication.
2. Open the setup page and switch to the Static ARP Table page.
3. Select the Enable ARP Table checkbox. Enter “192.168.1.6” in the No. 1 IP Address box, and its corresponding
MAC address is “00:18:23:10:00:35”.
DVP-PLC Operation Manual
45