7
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
7-5
Code Displayed Error Explanations Treatments
R1 setting error
Re-do the setting or execute the
Tuning function
Fan fault
Check whether the fan is blocked
Return to the factory
Power input phase-lacking
Phase-lacking within the
input power of the AC drive
Three imbalanced
conditions existed within
the input voltage
Check whether the power voltage
is normal
Check whether the screw at the
input power terminal is tightened
Other faults
Reserved
The motor parameter
-Tuning- failed
Re-check the wiring and reset the
parameter
Communication error
Check whether the communication
signal is counter-connected (RJ11)
Check whether the communication
form is correct
Upper and lower legs of
PWM are of the same LOW
level
Return to the factory
KEYPAD communication
overtime
Check whether the communication
circuit is well-conducted
RS485 communication
overtime
Check whether the communication
circuit is well-conducted