DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-19
Group 5: Motor Parameter
Control Mode
Parameters Functions Settings
Factory
Setting
VF VG SV SG T TG
05-00 Motor Auto Tuning
0: no function
1: measures (R1, R2,
Lm, Lc, no-load
current)
2: measures (R1, R2, Lc)
3: measures (R1, R2, Lc,
Lm, calculated by the
motor’s no-load
current)
0
{ { { { { {
05-01
Full-Load Current of
Motor 1
XXXA (30~120%)
A(100%)
{ { { { { {
05-02
No-Load Current of
Motor 1
XXXA (5~90%) A(40%)
° ° { { { {
a
05-03
Torque Compensation of
Motor 1 (for the V/F
Mode Only)
0.0~25.0% 0.0
{ { ° ° ° °
a
05-04
Slip Compensation of
Motor 1 (for V/F mode
only)
0.0~10.0% 0.0
{ { ° ° ° °
05-05
Number of Poles for
Motor 1
2~20 4
{ { { { { {
05-06
Line to Line resistance
R1 of Motor 1
mΩ
Xx
{ { { { { {
05-07
Rotor resistance R2 of
Motor 1
mΩ
Xx
° ° { { { {
05-08 LM of Motor 1 MH Xx
° ° { { { {
05-09 LC of Motor 1 MH Xx
° ° { { { {
a
05-10 Iron Loss of Motor 1 0.0~10.0% 1.5
° ° { { { {
05-11
Full-Load Current of
Motor 2
XXXA (30~120%)
A(100%)
{ { { { { {
05-12
No-Load Current of
Motor 2
XXXA (5~90%) A(40%)
° ° { { { {
a
05-13
Torque Compensation of
Motor 2
0.0~25.0% 0.0
{ { ° ° ° °
a
05-14
Slip Compensation of
Motor 2
0.0~10.0% 0.0
{ { ° ° ° °
05-15
Number of Poles for
Motor 2
2~20 4
{ { { { { {
05-16
Line to Line resistance
R1 of Motor 2
mΩ
Xx
{ { { { { {
05-17
Rotor resistance R2 of
Motor 2
mΩ
Xx
° ° { { { {
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Vista de pagina 136