Delta Electronics AC Motor Drive VFD-VE Series Especificaciones Pagina 71

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 182
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 70
5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-43
05-05 Number of Poles for Motor 1 Factory setting 4
Settings 2~20
This parameter sets the number of poles of your motor (must be an even number).
05-06 Line to Line resistance R1 of Motor 1 Factory setting X
X
Settings m
05-07 Rotor resistance R2 of Motor 1 Factory setting X
X
Settings m
05-08 LM of Motor 1 Factory setting X
X
Settings MH
05-09 LC of Motor 1 Factory setting X
X
Settings MH
The settings of Pr.05-05 to 05-09 depend on the current rating of the inverter and the auto
tune feature. Please do not change these settings as incorrect performance may occur.
05-10 Iron Loss of Motor 1
a
Factory setting 1.5
Settings 0.0~10.0%
This parameter is defined as the percentage of the rated power.
05-11 Full-Load Current of Motor 2 Factory setting A(100%)
Settings XXXA(30~120%)
05-12 No-Load Current of Motor 2 Factory setting A(40%)
Settings XXXA(5~90%)
05-13 Torque Compensation of Motor 2
a
Factory setting 0.0
Settings 0.0~25.0%
05-14 Slip Compensation of Motor 2
a
Factory setting 0.0
Settings 0.0~10.0%
05-15 Number of Poles for Motor 2 Factory setting 4
Settings 2~20
05-16 Line to Line resistance R1 of Motor 2 Factory setting X
X
Settings m
05-17 Rotor resistance R2 of Motor 2 Factory setting X
X
Settings m
05-18 LM of Motor 2 Factory setting X
X
Settings MH