Delta Electronics AC Motor Drive VFD-VE Series Especificaciones Pagina 35

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 182
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 34
5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-7
4: Torque control: Enables Torque (current) Control. Torque control allows the user to run
the AC drive based on current instead of frequency.
5: Torque control + PG: Enables the Closed Loop Torque Control. This will increase the
torque accuracy throughout the speed range and disabled Pr. 05-04.
Note: PI values for PG (closed loop), vector control (open loop) and torque control are
determined by Pr. 05-21~05-25.
00-11
Forward Reverse transition in V/F mode
Factory setting 0
Settings 0
Follow Pr. 01-00 to
01-08 Settings
Do not skip the start-up frequency
1
Follow Pr. 01-00 to
01-08 Settings
Skip the start-up frequency
2 V/F1.5 power curve Do not skip the start-up frequency
3 V/F1.5 power curve Skip the start-up frequency
4 2 power curve Do not skip the start-up frequency
5 2 power curve Skip the start-up frequency
Frequenc
y
01-09
Startup
Frequency
FWD RUN
STOP
FWD RUN
REV RUN
Going through point 0
Time
01-09
Startup
Frequency
FWD RUN
REV RUN
STOP
FWD RUN
REV RUN
Not going through point 0
-01-09
V/F Mode bit=0
V/F Mode bit=1
REV RUN
This parameter selects the transition mode between Forward and Reverse. By
skipping the start up frequency range, there will be a short time where the motor has not
flux and very little power. It is recommended for all non-horizontal movement to
choose “do not skip the start up frequency”.
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Vista de pagina 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 181 182

Comentarios a estos manuales

Sin comentarios