Delta Electronics AC Motor Drive VFD-VE Series Especificaciones Pagina 144

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 182
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 143
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-26
Group 8: High-Performance Parameter
Control Mode
Parameters Functions Settings
Factory
Setting
VF VG SV SG T TG
a
08-00
PID Feedback
Terminal
Selection
0: Disable
1: AVI (0~10V)
2: ACI (4~20mA)
3: AUI ( +/-10V)
4: Clock (F/R--master speed)
5: Clock (F/R--A/B direction)
0
{ { { { { {
a
08-01
Proportional Gain
(P)
0.0~500.0%
80.0
{ { { { { {
0.00~100.00 Sec
a
08-02 Integral Time (I)
0.00: no integral
1.00
{
{
{
{
{
{
{
{
{
{
{
{
a
08-03
Differential Time
(D)
0.00~1.00 Sec
0.00
{ { { { { {
a
08-04
Integration’s
Upper Bound
Frequency
0.0~100.0%
100.0
{ { { { { {
a
08-05
PID Frequency
Output Command
limit
0.0~100.0%
100.0
{ { { { { {
a
08-06
PID Deviation
Range
-100.0~+100.0%
0.0
{ { { { { {
a
08-07 One-Time Delay
0.000~0.005 Sec
0.000
{ { { { { {
a
08-08
Detection Time of
the Feedback
Error
0.0~6000.0 Sec
0.0
{ { { { { {
a
08-09
Feedback Signal
Fault Treatment
0: warn and keep operating
1: warn and RAMP to stop
2: warn and COAST to stop
0
{ { { { { {
a
08-10
Dwell (sleep)
Frequency
0.00~400.00Hz
0.00
{ { { { ° °
a
08-11
Revival
Frequency
0.00~400.00Hz
0.00
{ { { { ° °
a
08-12
Dwell (sleep)
Period
0.0~6000.0 Sec
0.0
{ { { { ° °
a
08-13
Fan control
0: when power is applied, the fan
will turn on
1:When the run command is given,
the fan will turn on
0
{ { { { { {