8
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-17
Control Mode
Parameters Functions Settings
Factory
Setting
VF VG SV SG T TG
a
04-27
Time Duration of PCO
Step 12
0.0~65500 Sec 0.0
{ { { { ° °
a
04-28
Time Duration of PCO
Step 13
0.0~65500 Sec 0.0
{ { { { ° °
a
04-29
Time Duration of PCO
Step 14
0.0~65500 Sec 0.0
{ { { { ° °
a
04-30
Time Duration of PCO
Step 15
0.0~65500 Sec 0.0
{ { { { ° °
a
04-31 The PCO Time Multiplier 1~10 1
{ { { { ° °
a
04-32
The PCO Operation
Direction
0~32767 (0: FWD; 1: REV) 0
{ { { { ° °
a
04-33
Process Control
Operation Mode
Bit0=0: direction determined
by Pr. 04-32
Bit0=1: direction determined
by the master speed
control
Bit1=0: continuously
execute the process
control operation
Bit1=1: execute only one
process control
operation cycle
Bit2=0: zero speed intervals
disabled
Bit2=1: zero speed intervals
enabled
Bit3=0: operate at zero
speed upon time
extension
Bit3=1: operate at a
constant speed
upon time extension
Bit4=0: PCO disabled
Bit4=1: PCO enabled
00000
{ { { { ° °