VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-4
Parameter
Explanation Settings
Factory
Setting
Customer
20: No function
21: RESET command (N.C)
22: Control source: External Terminal
23: Control source: Keypad
24: Control source: Communication
25: Parameter Lock (Write disable, Read
is always 0)
26: PID Disable (N.O.)
27: PID Disable (N.C.)
28: Second Source for Frequency
Command
29: Forward (contact is open) / Reverse
(contact is close)
30: One-Shot PLC Run
31: Index input signal
32: Counter Incremented by Drive Output
Frequency
a
Pr.43
Analog Output
Signal
00: Analog Frequency Meter (0 to
Maximum Output Frequency)
01: Analog Current Meter (0 to 250% of
the rated AC drive current)
02: Feedback signal (0 - 100%)
03: Output power (0 - 100%)
00
a
Pr.44
Analog Output Gain 00 to 200 %
100
Pr.45
Pr.46
Multi-Function
Output Terminal 1
(Photocoupler
output)
Multi-function Output
Terminal 2
(Relay Output)
00: AC Drive Operational
01: Maximum Output Frequency Attained
02: Zero Speed
03: Over-Torque Detection
04: Base-Block (B.B) Indication
05: Low Voltage Indication
06: AC Drive Operation Mode
07: Fault Indication
08: Desired Frequency Attained
09: PLC Program Running
10: PLC Program Step Completed
11: PLC Program Completed
12: PLC Operation Paused
13: Top Count Value Attained
14: Preliminary Counter Value Attained
15: Warning (PID feedback loss,
communication error)
16: Below the Desired Frequency
17: PID supervision
18: Over Voltage supervision
19: Over Heat supervision
20: Over Current stall supervision
00