VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-44
3.3 ADR (Communication Address)
Valid communication addresses are in the range of 0 to 254. An address equals to 0
means a broadcast to all AC drives (AMD) in the network. In this case, the AMD will
not reply to the master device.
For example, communication to AMD with address 16 decimal:
ASCII mode: (ADR 1, ADR 0)=’1’,’0’ => ‘1’=31H, ‘0’=30H
RTU mode: (ADR)=10H
3.4 CMD (Command code) and DATA (data characters)
The format of data characters depends on the command code. The available command
codes are described as followed: Command code: 03H, read N words. The maximum
value of N is 12. For example, reading continuous 2 words from starting address 2102H
of AMD with address 01H.
ASCII mode:
Command message: Response message:
STX ‘:’ STX ‘:’
‘0’ ‘0’ ADR 1
ADR 0
‘1’
ADR 1
ADR 0
‘1’
‘0’ ‘0’ CMD 1
CMD 0
‘3’
CMD 1
CMD 0
‘3’
‘2’ ‘0’
‘1’
Number of data
(Count by byte)
‘4’
‘0’ ‘1’
Starting data
address
‘2’ ‘7’
‘0’ ‘7’
‘0’
Content of starting
data address
2102H
‘0’
‘0’ ‘0’
Number of data
(Count by word)
‘2’ ‘0’
‘D’ ‘0’ LRC CHK 1
LRC CHK 0
‘7’
Content of data
address 2103H
‘0’
CR ‘7’ END 1
END 0
LF
LRC CHK 1
LRC CHK 0
‘1’
CR
END 1
END 0
LF