5
VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-25
LT
LT
BZ
RA
RB
RC
MO1
MCM
Multi-function indication
output terminals.
AC 250V 2A
DC 30V 2A
Multi-function PHC
output terminals.
PHC
480VDC 50mA
Pre-set freq. attained
Plus terminals
Power 48VDC
50mA
Minus terminal
Power source
AC/DC
Faults indication.
Power indication.
Pr.47
Desired Frequency Attained
a
Factory Setting: 0.00
Settings 0.00 to 400.0 Hz Unit: 0.1Hz
This parameter allows monitoring a certain frequency and then activates one of the
Multi-function output terminals (Pr.45 or Pr.46 set to 8) when that frequency is achieved.
Desired Freq.
Detection
range
-2Hz
Detection
range
+
-
4Hz
Detection range
+
-
2Hz
Time
Freq.
Max. Output
Freq.
ON
ON
OFF
OFF
OFF
OFF
Preset Freq.
Attained
Indication
Pr.45 to
Pr.46
Desired Freq.
Attained
Indication
Pr.45 & Pr.46
Desired Freq. Attained & Preset Freq. Attained
Pr.47
Pr.48
Adjust Bias of External Input Frequency
a
Factory Setting: 0.00 Hz
Settings 0.00 to 200.0% Unit: 0.1Hz
This parameter provides a frequency offset when the source of frequency command is
the analog input.