VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
A-2
Voltage Class
460V Class
3-phase
Rated Input Current (A)
4.2 5.7 6.0 8.5 14 23
Rated Voltage 3-phase 380 to 480 V
Voltage Tolerance
10%(342~528 V)
Input Rating
Frequency Tolerance
5%(47~63 Hz)
Cooling Method Fan Cooled
Weight (kg) 1.5 1.5 2.0 3.2 3.2 3.3
Voltage Class
575V Class
Model Number VFD-XXXM 007 015 022 037 055 075
Max. Applicable Motor Output
(kW)
0.75 1.5 2.2 3.7 5.5 7.5
Max. Applicable Motor Output
(hp)
1.0 2.0 3.0 5.0 7.5 10
Rated Output Capacity
(kVA)
1.7 3.0 4.2 6.6 9.9 12.2
Rated Output Current (A)
1.7 3.0 4.2 6.6 9.9 12.2
Maximum Output Voltage
(V)
3-phase Proportional to Input Voltage
Output Frequency (Hz)
0.1~400 Hz
Output Rating
Carrier Frequency (kHz)
1-10
3-phase
Rated Input Current (A)
2.4 4.2 5.9 7.0 10.5 12.9
Rated Voltage 3-phase 500 to 600 V
Voltage Tolerance -15% ~ +10%(425~660 V)
Input Rating
Frequency Tolerance
5%(47~63 Hz)
Cooling Method Fan Cooled
Weight (kg) 1.5 1.5 2.0 3.2 3.2 3.3
General Specifications
Control System SPWM (Sinusoidal Pulse Width Modulation) control (V/F or sensorless vector control)
Freq. Setting
Resolution
0.1Hz
Output Frequency
Resolution
0.1Hz
Torque
Characteristics
Including the auto-torque, auto-slip compensation; starting torque can be 150% at
5.0Hz
Overload Endurance 150% of rated current for 1 minute
Skip Frequency Three zones, settings range 0.1-400Hz
Accel/Decel Time 0.1 to 600 seconds (4 Independent settings for Accel/Decel Time)
Stall Prevention Level
Frequency Setting
20 to 200%, Setting of Rated Current
DC Injection Braking
Operation frequency 0-60Hz, output 0-100% rated current
Start time 0-5 seconds, stop time 0-25 seconds
Braking Torque
Approx. 20% (up to 125% possible with option braking resistor or braking unit
externally mounted, 1-15HP braking transistor built-in)
Control Characteristics
V/F Pattern Adjustable V/F pattern
Keypad Setting by
Frequency
Setting
External
Signal
Potentiometer-5KΩ/0.5W, 0 to +10VDC, 4 to 20mA RS-485 interface; Multi-Function
Inputs 0 to 5 (7 steps, Jog, up/down)
Characteri
Operation Keypad Set by RUN, STOP
Comentarios a estos manuales