
VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-6
Parameter
Explanation Settings
Factory
Setting
Customer
Pr.61
Over-Torque
Detection Level
30 to 200 %
150
Pr.62
Over-Torque
Detection Time
0.0 to 10.0 seconds
0.1
Pr.63
Loss of ACI
(4-20mA)
00: Decelerate to 0 Hz
01: Stop immediately and display "EF"
02: Continue operation by last frequency
command
00
a
Pr.64
User Defined
Function for Display
00: Display AC drive output Frequency
(Hz)
01: Display User-defined output
Frequency (H*Pr.65)
02: Output Voltage (E)
03: DC Bus Voltage (u_)
04: PV (i)
05: Display the value of internal counter
(c)
06: Display the setting frequency (F or
o=%)
07: Display the parameter setting (Pr.00)
08:
Reserved
09: Output Current (A)
10: Display program operation (0.xxx),
Fwd, or Rev
06
a
Pr.65
Coefficient K
0.01 to 160.0
1.00
a
Pr.66
Communication
Frequency
0.00 to 400.0 Hz
0.00
Pr.67
Skip Frequency 1
0.00 to 400.0 Hz
0.00
Pr.68
Skip Frequency 2
0.00 to 400.0 Hz
0.00
Pr.69
Skip Frequency 3
0.00 to 400.0 Hz
0.00
Pr.70
Skip Frequency Band
0.00 to 20.00 Hz
0.00
115V/230V/460V series: 01 to 15
(The factory setting of
VFD075M43A is
10)
15
Pr.71
PWM Carrier
Frequency
575V series: 01 to 10
6
Pr.72
Auto Restart
Attempts after Fault
00 to 10
00
Comentarios a estos manuales