Fault
Name
Fault Descriptions
Corrective Actions
Drive’s internal circuitry
abnormal.
1. Switch off power supply.
2. Check whether the input voltage falls within
the rated AC drive input voltage. Switch on
the AC drive.
The external terminal EF-GND
goes from OFF to ON.
When external terminal EF-GND is closed, the
output will be turned off (under N.O. E.F.).
Auto accel/decel failure
Don’t use the function of auto acceleration/
deceleration.
Ground fault :
The AC drive output is abnormal.
When the output terminal is
grounded (short circuit current is
50% more than the AC drive
rated current), the AC drive
power module may be damaged.
The short circuit protection is
provided for AC drive protection,
not user protection.
Ground fault :
1. Check whether the IGBT power module is
damaged.
2. Check for possible poor insulation at the
output line.
Communication Error
Please refer to Pr.92.
1. Check the connection between the AC drive
and computer for loose wires.
2. Check if the communication protocol is
properly set.
External Base Block.
AC drive output is turned off.
1. When the external input terminal (base-block)
is active, the AC drive output will be turned off.
2. Disable this connection and the AC drive will
begin to work again.