Parameters Explanation Settings
Factory
Setting
2-01
Source of Operation
Command
d0: by Digital Keypad
d1: by external terminals, keypad STOP
enabled
d2: by external terminals, keypad STOP
disabled
d3: by RS-485 communication interface,
keypad STOP enabled
d4: by RS-485 communication interface,
keypad STOP disabled
d0
2-02 Stop Method
d0: Ramp Stop
d1: Coast Stop
d0
2-03 PWM Carrier Frequency
d3: 3KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
d7: 7KHz
d8: 8KHz
d9: 9KHz
d10: 10KHz
d10
2-04
Reverse Operation d0: Enable REV
d1: Disable REV
d0
2-05 Loss of ACI Signal
d0: 0 Hz, continue running
d1: Stop the frequency output
d2: Last ACI input command
d0
2-06
Analog Auxiliary
Frequency Operation
d0: Disable
d1: Enable + AVI
d2: Enable + ACI
d0