Group 6 Protection Parameters
Parameters Explanation Settings
Factory
Setting
d0: Disable
6-00
Over-Voltage Stall
Prevention
d1: Enable
d1
230V series: d350 to d410V d390
6-01
Over-Voltage Prevention
Level
460V series: d700 to d820V d780
6-02
Over-Current Stall
Prevention Level
d20 to d150% d130
d0: Disabled
d1: Enabled during constant speed
operation and continue to run to OL1
or OL.
d2: Enabled during Constant Speed
Operation and halted after detection
d3: Enabled during running and continues
before Continuous Output Time Limit
(Pr.6-05) is reached
6-03
Over-Torque Detection
Mode
d4: Enabled during running and halted
after Over-Torque detection
d0
6-04
Over-Torque Detection
Level
d30 to d200% d150
6-05
Time setting for
Over-torque Detection
d0.1 to d10.0 Sec d0.1
6-06
Electronic Thermal
Overload Relay Selection
d0 to d2 d2
6-07
Electronic Thermal
Characteristic
!
d30 to d600 Sec d60
6-08 Present Fault Record d0: No Fault occurred
6-09 Second Most Recent
Fault Record
d1: Over Current (oc)
d2: Over Voltage (ov)
d3: Over Heat (oH)
6-10
Third Most Recent Fault
Record
d4: Over Load (oL)
d0
d5: Over Load (oL1)
d6: External Fault (EF)
d7: Not used
d8: Not used
d9: Current exceed during Acceleration
(ocA)
d10: Current exceed during Deceleration
(ocd)
d11: Current exceed during Steady State
(ocn)
d12: Ground Fault (GF)