Delta Electronics Network Device VFD-S Especificaciones Pagina 108

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 143
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 107
8
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-11
Group 9: Communication Parameters
Parameters Explanation Settings
Factory
Setting
9-00
Communication
Address
!
d1 to d254 d1
d0: Baud Rate 4800 bps
d1: Baud Rate 9600 bps
d2: Baud Rate 19200 bps
9-01 Transmission Speed
!
d3: Baud Rate 38400 bps
d1
d0: Warn and Keep Operating
d1: Warn and Ramp to Stop
d2: Warn and Coast to Stop
9-02
Transmission Fault
Treatment
!
d3: Keep Operating without Warning
d0
d0: Disable
9-03
Modbus Communication
Watchdog Timer
!
d1 to d20: time setting (1 sec increment)
d0
d0: 7,N,2 (Modbus, ASCII)
d1: 7,E,1 (Modbus, ASCII)
d2: 7,O,1 (Modbus, ASCII)
d3: 8,N,2 (Modbus, ASCII)
d4: 8,E,1 (Modbus, ASCII)
d5: 8,O,1 (Modbus, ASCII)
d6: 8,N,2 (Modbus, RTU)
d7: 8,E,1 (Modbus, RTU)
9-04
Communication
Protocol
!
d8: 8,O,1 (Modbus, RTU)
d0