5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-19
Function Explanations:
d 0 Not Used.
d 1 AC drive operational:
the output terminal will be activated when the drive is running.
d 2 Maximum Output Frequency Attained:
the output will be activated when the AC drive
attains Maximum Output Frequency.
d 3
Zero speed:
the output will be activated when Command Frequency is lower than the
Minimum Output Frequency.
d 4
Over-Torque Detection:
the output will be activated as long as the over-torque is
detected. Pr.6-04 determines the Over-Torque detection level.
d 5
Base-Block (B.B.) Indication:
the output will be activated when the output of the AC
drive is shut off by external Baseblock.
d 6
Low Voltage Indication:
the output will be activated when low voltage is detected.
d 7
AC Drive Operation Mode:
the output will be activated when the operation of the AC
drive is controlled by External Control Terminals.
d 8
Fault Indication:
the output will be activated when faults occur (oc, ov, oH, oL, oL1, EF,
cF3, HPF, ocA, ocd, ocn, GF).
d 9
Desired Frequency Attained:
the output will be activated when the desired frequency
(Pr.3-02)is attained.
d10
PLC Program Running:
the output will be activated when the PLC program is running.
d11
PLC Program Step Completed:
the output will be activated for 0.5 sec. when each
multi-step speed is attained.
d12
PLC Program completed:
the output will be activated for 0.5 sec. when the PLC
program cycle has completed.
d13
PLC Program Operation Paused:
the output will be activated when PLC operation is
paused.
d14
Terminal Count Value Attained:
counter reaches Terminal Count Value.
d15
Preliminary Count Value Attained:
counter reaches Preliminary Count Value.
d16
Ready State Indicator.
d17 FWD command indication: When AC drive receives the command of forward
running, it will output immediately no matter AC drive is in the state of run or stop.
d18 REV command indication: When AC drive receives the command of reverse
running, it will output immediately no matter AC drive is in the state of run or stop.