0 - 03 Start-up Display Selection Factory Setting: d 0
Settings d 0 Display the Master Frequency (F)
d 1 Display the actual output frequency (H)
d 2 Display the content of users-defined unit
d 3 Display the output current (A)
This parameter can be set during operation.
0 - 04 Content of User Defined Unit Factory Setting: d 0
Settings d 0 Display the user-defined unit (u)
d 1 Display the counter value (C)
d 2 Display the content of PLC time (1 = tt)
d 3 Display the DC BUS voltage (U)
d 4 Display the output voltage (E)
d 5 Display frequency commands of PID (P)
d 6 Display PID feedback (after multiplying by Gain) (b)
This parameter can be set during operation.
Note: Display the user-defined unit, where unit = H X
0 - 05 User Defined Coefficient K Factory Setting: d 1.0
Settings d 0.1 to d 160 Unit: 0.1
This parameter can be set during operation.
The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
Display value = (output frequency x K)
The display window is only capable of showing three digits, yet you could use Pr.0-05 to
create larger numbers. The display windows uses decimal points to signify numbers up
to five digits as illustrated in the next page: