Delta Electronics Network Device VFD-S Especificaciones Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 143
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-2
0 - 03 Start-up Display Selection Factory Setting: d 0
Settings d 0 Display the Master Frequency (F)
d 1 Display the actual output frequency (H)
d 2 Display the content of users-defined unit
d 3 Display the output current (A
This parameter can be set during operation.
0 - 04 Content of User Defined Unit Factory Setting: d 0
Settings d 0 Display the user-defined unit (u)
d 1 Display the counter value (C)
d 2 Display the content of PLC time (1 = tt)
d 3 Display the DC BUS voltage (U)
d 4 Display the output voltage (E)
d 5 Display frequency commands of PID (P)
d 6 Display PID feedback (after multiplying by Gain) (b)
This parameter can be set during operation.
Note: Display the user-defined unit, where unit = H X
0 - 05 User Defined Coefficient K Factory Setting: d 1.0
Settings d 0.1 to d 160 Unit: 0.1
This parameter can be set during operation.
The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
Display value = (output frequency x K)
The display window is only capable of showing three digits, yet you could use Pr.0-05 to
create larger numbers. The display windows uses decimal points to signify numbers up
to five digits as illustrated in the next page:
0-05
Vista de pagina 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 142 143

Comentarios a estos manuales

Sin comentarios