5.3 Group 2: Operation Method Parameters
2 – 00 Source of Frequency Command Factory Setting: d 0
Settings d 0 Master Frequency input determined by digital keypad.
(record the frequency of power loss and it can do analog
overlap plus)
d 1 Master Frequency determined by analog signal DC 0V-10V
(external terminal AVI). (won’t record the frequency of power
loss and it can’t do analog overlap plus)
d 2 Master Frequency determined by analog signal DC 4mA -
20mA (external terminal AVI). (won’t record the frequency of
power loss and it can’t do analog overlap plus)
d 3 Master Frequency determined by Potentiometer on the
digital keypad. (won’t record the frequency of power loss
and it can do analog overlap plus)
d 4 Master Frequency operated by RS-485 serial
communication interface and record frequency of power
loss. (record the frequency of power loss and it can do
analog overlap plus)
d 5 Master Frequency operated by RS-485 serial
communication interface and won’t record frequency before
power loss. (won’t record the frequency of power loss and it
can do analog overlap plus)
This parameter sets the Frequency Command Source of the AC drive.
If the Frequency Command Source is external (DC 0 to +10V or 4 to 20mA), please
make sure the (AVI) terminal jumper is in the proper position as shown below.
Position of jumper: Please open the top cover. It is at the lower-left corner of the panel.
The jumper J1 determines the type of external analog input, either DC voltage signal or
current signal.