VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-10
Group 7 Motor Parameters
Parameters Explanation Settings
Factory
Setting
7-00 Motor Rated Current
!
d30 to d120% d85
7-01 Motor No-Load Current
!
d0 to d90% d50
7-02
Torque Compensation
!
d0 to d10 d01
7-03 Slip Compensation
!
d0.0 to d10.0 d0.0
Group 8 Special Parameters
Parameters Explanation Settings
Factory
Setting
8-00 DC Braking Voltage Level d0 to d30% d0
8-01 DC Braking Time during Start-Up d0.0 to d60.0 Sec d0.0
8-02 DC Braking time during Stopping d0.0 to d60.0 Sec d0.0
8-03 Start-Point for DC Braking d0.0 to d400 Hz d0.0
d0: Stop Operation after
Momentary Power Loss
d1: Continues after Momentary
Power Loss, speed search
starts with Master
Frequency
8-04
Momentary Power Loss Operation
Selection
d2: Continues after Momentary
Power Loss, speed search
starts with Minimum
Output Frequency
d0
8-05
Maximum Allowable Power Loss
Time
d0.3 to d5.0 Sec d2.0
8-06 B.B. Time for Speed Search d0.3 to d5.0 Sec d0.5
8-07
Maximum Speed Search Current
Level
d30 to d200% d150
8-08 Skip Frequency 1 Upper Bound d0.0 to d400 Hz d0.0
8-09 Skip Frequency 1 Lower Bound d0.0 to d400 Hz d0.0
8-10 Skip Frequency 2 Upper Bound d0.0 to d400 Hz d0.0
8-11 Skip Frequency 2 Lower bound d0.0 to d400 Hz d0.0
8-12 Skip Frequency 3 Upper bound d0.0 to d400 Hz d0.0
8-13 Skip Frequency 3 Lower Bound d0.0 to d400 Hz d0.0
8-14 Auto Restart After Fault d0 to d10 d0
d0: AVR Function Enable
d1: AVR Function Disable
8-15 AVR Function
d2: AVR Function Disable when
Deceleration
d2
8-16 Dynamic Braking Voltage d350 to d450V* d380*
8-17 DC Braking Lower Bound Limit d0.0 to d400 Hz d0.0