Chapter 7 Servo Parameters|ASDA-B Series
7-46 Revision February 2008, Doc. Name: 2006PDD23000009
P2 - 24
DPH
Notch Filter Attenuation Rate
(Resonance Suppression)
Communication Addr.: 0218H
Default: 0 Related Section:
Applicable Control Mode: P/S/T Section 6.3.7, P2-23
Unit: dB
Unit: Hz
Range: 0 ~ 32
Settings:
0: Disabled
P2 - 25
NLP
Low-pass Filter Time Constant
(Resonance Suppression)
Communication Addr.: 0219H
Default: 20 Related Section:
Applicable Control Mode: P/S/T Section 6.3.7, P2-32
Unit: 0.1ms
Range: 0 ~ 10000
Settings:
This parameter is used to set low-pass filter time constant of resonance suppression.
0: Disabled
P2 - 26
DST External Anti-Interference Gain Communication Addr.: 021AH
Default: 0 Related Section:
Applicable Control Mode: P/S/T Section 6.3.7, P2-32
Unit: N/A
Range: 0 ~ 511
Settings:
0: Disabled