Chapter 7 Servo Parameters|ASDA-B Series
7-70 Revision February 2008, Doc. Name: 2006PDD23000009
4: Baud rate 57600 (data transmission speed: bits / second)
5: Baud rate 115200 (data transmission speed: bits / second)
P8 - 07 KPTL Communication Protocol (Keypad) Communication Addr.: 0807H
Default: 0 Related Section: N/A
Applicable Control Mode: P/S/T
Unit: N/A
Range: 0 ~ 8
Settings:
0: Modbus ASCII mode, <7,N,2>
1: Modbus ASCII mode, <7,E,1 >
2: Modbus ASCII mode, <7,O,1>
3: Modbus ASCII mode, <8,N,2 >
4: Modbus ASCII mode, <8,E,1>
5: Modbus ASCII mode, <8,O,1>
6: Modbus RTU mode, <8,N,2>
7: Modbus RTU mode, <8,E,1>
8: Modbus RTU mode, <8,O,1>
P8 - 08 KCMM Communication Selection (Keypad) Communication Addr.: 0808H
Default: 0 Related Section: N/A
Applicable Control Mode: P/S/T
Unit: N/A
Range: 0 ~ 1
Settings:
0: RS-232
1: RS-485
Multiple communication modes RS-232, RS-485 cannot be used within one communication ring.
P8 - 09 KTST Keypad Hardware Testing Communication Addr.: 0809H
Default: 0 Related Section: N/A
Applicable Control Mode: P/S/T
Unit: N/A
Range: 0 ~ 4
Settings:
0: Disabled.
1: Function key testing. Pressing MODE key can exit this testing mode.