
5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-71
Settings 0.0~2.5 Sec Unit: 0.1
This parameter determines primary Low Pass filter time.
Output frequency of PID controller will filter by primary low pass function. This function could
decrease change of output frequency. A long primary low pass time means filter degree is high and
vice versa.
Unsuitable primary low pass filter time setting may cause system oscillation.
10 - 08
PID Feedback Signal Range
Factory Setting: 600.0
Settings 0.0~6550.0 Unit:0.1
This parameter setting could allow the maximum of PID deviation.
If PID function is normal, it should control the detective value to target value accurately in the
certain time. If AC drive can’t control deviation in the 10-08 setting range during 10-09 setting time,
FbL warning will pup-up and it means PID feedback control is abnormal. The treatment is set as
10-10.
10 - 09
PID Feedback Signal Fault Treatment Time
Factory Setting: 0.0
Settings 0.0~3600.0 Sec Unit: 0.1
This parameter is to set the detection time of abnormal PID derivative. If PID deviation detection
time is set to 0.0, the function is disabled.
10 - 10
PID Feedback Signal Fault Treatment
Factory Setting: 01
Settings 00: Warn and RAMP stop
01: Warn and COAST stop
02: Warn and keep operating
This parameter is to set treatment of the abnormal PID deviation.
10 - 11
PID Minimum Output Frequency
Factory Setting: 01
Settings 0: By PID controller
1: By AC drive
This parameter can decide the source of PID output minimum frequency when AC drive enters PID
sleep process. If it is set to 0, minimum output frequency should be set by PID. If it is set to 1 and
01-08 is 0, the output frequency is equal to the value of 01-05 setting. If it is set to 1 and 01-08 is not
0, the output frequency is equal to the value of 01-08 setting.
Comentarios a estos manuales