VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-28
5.6 Group 5: Multi-step Speed Frequency Parameters
05 - 00
1
st
Step Speed Frequency
Factory Setting: 0.00
05 - 01
2nd Step Speed Frequency
Factory Setting: 0.00
05 - 02
3rd Step Speed Frequency
Factory Setting: 0.00
05 - 03
4th Step Speed Frequency
Factory Setting: 0.00
05 - 04
5th Step Speed Frequency
Factory Setting: 0.00
05 - 05
6th Step Speed Frequency
Factory Setting: 0.00
05 - 06
7th Step Speed Frequency
Factory Setting: 0.00
05 - 07
8th Step Speed Frequency
Factory Setting: 0.00
05 - 08
9th Step Speed Frequency
Factory Setting: 0.00
05 - 09 10th Step Speed Frequency
Factory Setting: 0.00
05 - 10
11th Step Speed Frequency
Factory Setting: 0.00
05 - 11
12th Step Speed Frequency
Factory Setting: 0.00
05 - 12
13th Step Speed Frequency
Factory Setting: 0.00
05 - 13
14th Step Speed Frequency
Factory Setting: 0.00
05 - 14
15th Step Speed Frequency
Factory Setting: 0.00
Settings 0.00~120.00 Hz Unit: 0.01
The Multi-Function Input Terminals (refer to Pr.04-00 to 04-07) are used to select one of the AC
drive Multi-Step speeds. The speeds (frequencies) are determined by Pr.05-00 to 05-14 shown
above.
05 - 15
PLC Mode
Factory Setting: 00
Settings 00 Disable PLC operation
01 Execute one program cycle
02 Continuously execute program cycles
03 Execute one program cycle step by step
04 Continuously execute program cycles step by step
This parameter selects the mode of PLC operation for the AC drive. The AC drive will change
speeds and directions according to the users desired programming.