5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-83
11 - 09
Wake Up Frequency of Sleep Process
Factory Setting: 0.00
Settings 0.00 to 120.00Hz Unit: 0.01
This parameter determines wake up frequency after AC drive enters sleep process.
PID control function will keep calculating frequency command (F) when AC drive is in sleep
process. When frequency command attains to wake up frequency, AC drive will accelerate from
01-05 minimum frequency setting according to V/f curve.
The setting of wake up frequency needs to be greater than sleep frequency.
The Sleep feedback rate of Sleep Process has to be bigger than Wake up feedback rate of Sleep
Process.
When Pr11-12 =1, this parameter is a certain percentage of PID rate.
eedback
otor frequency
arget
-
-
[-]
[-]
[-]+
seconds