Delta Electronics AC Drive VFD-F Series Especificaciones Pagina 53

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 190
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 52
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-20
03 - 15
DC Fan Control
Factory Setting: 00
Settings
00: Fan runs on power up.
01: Fan begins upon a RUN command. Fan stops 1 minute after a STOP
command.
02: Fan begins upon a RUN command. Fan stops after a STOP command
03: Fan is controlled by temperature. Approximately a 60°C temperature will
start the fan.
04: Unusual Fan status warning, inverter continues to run.
(This setting is only available in the existing firmware v.3.104,
the new released version v.1.302 and the versions above v.1.302)
This parameter determines DC fan control method.
Vista de pagina 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 189 190

Comentarios a estos manuales

Sin comentarios