Speed Search Time
Factory Setting: 0.5
Settings 0.1~5.0 Sec Unit: 0.1
This parameter determines the delay time from fault (power loss, OV, OC or BB) recovery to start to
execute the function of speed search time.
08 - 07
Maximum Speed Search Current
Factory Setting: 110
Settings 30~150% Unit: 1
This parameter determines maximum current of speed search.
Maximum speed search current will have influence with synchronization attained time. The greater
this parameter is set, the faster it will be synchronization. But if the parameter setting value is too
great, it may cause over-loaded protection.
If 08-04 is set to 01: when speed search is from top downward, output frequency is searched from
master frequency command downward. Now output voltage and output current will be added from
zero. When output current is equal to 08-07 setting value, AC drive output current will retain in a
fixed value and output frequency will keep on searching from top downward. When output
frequency and output voltage is overlapped with V/f setting frequency, AC drive will judge that is
synchronization attained and accelerates from V/f curve to master frequency command.
If 08-04 is set to 02: AC drive will accelerate according to V/f curve and won’t do any special
treatment.
Power
Input
Output
Frequency
Output
Voltage
B.B. Time
08-06
Speed Search
Speed
Synchronization
Detection
Momentary Power Loss Operation
Maximum allowable
power loss time
08-05
08-04=01
B.B.Time
08-06
Max. Allowable
Power Loss Time
08-05
08-04=02