
5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-37
chart below. The actual reaction time will vary depending on output current.
1
2
3
4
5
60Hz or more
50Hz
10Hz
5Hz
Load
factor
(%)
Operation
Time(min)
0
20
40
60
80
100
120
140
160
180 200
06 - 08
Low Current Detection Level
Factory Setting: 00
Settings 00~100% (00 disabled) Unit: 1
06 - 09
Low Current Detection Time
Factory Setting: 10.0
Settings 0.1~ 3600.0 Sec Unit: 0.1
06 - 10
Low Current Detection Treatment
Factory Setting: 01
Settings
00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating
These parameters set the low current detection mode, time, and operation.
06 - 11
Present Fault Record
Factory Setting: 00
06 - 12
Second Most Recent Fault Record
Factory Setting: 00
06 - 13
Third Most Recent Fault Record
Factory Setting: 00
06 - 14
Fourth Recent Fault Record
Factory Setting: 00
Settings 00 No fault occurred
01 Over-current (oc)
02 Over-voltage (ov)
03 Overheat (oH)
04 Overload (oL)
05 Electronic thermal relay (oL1)
06 External fault (EF)
07 AC drive IGBT fault (occ)
Comentarios a estos manuales