Setting Functions Descriptions
40 HOA-Off mode indication
Under the Off mode indication of HOA mode, the
corresponding relay output will be closed.
41 HOA-Auto mode indication
Under the Automatic mode indication of HOA
mode, the corresponding relay output will be
closed.
42 Fire mode indication
When Fire mode indication is activated, the
corresponding relay output will be closed.
43 Bypass fire mode indication
Under the Bypass fire mode indication, the
corresponding relay output will be closed.
The VFD-F has two form C relays (multi-function output 1 and 2). There is an optional External
Relay Card with 6 NO contact relays (multi-function outputs 3-8).
External relay specifications = 8A/250VAC or 5A/30VDC.
Relay delay time is 5~10 msec.
03 - 08
Master Frequency Attained 1
Factory Setting: 0.00
03 - 09
Master Frequency Attained 2
Settings 0.00~120.00 Hz Unit: 0.01
An output relay may be programmed to activate when the output frequency exceeds the desired
attained frequency setting of these two parameters.
There is a
2Hz window of operation. If the master frequency attained is 20Hz and the output
frequency exceeds 20Hz, the corresponding output relay will be “closed”. When the output
frequency is less than 18Hz, the corresponding output relay will be “opened” as the following
diagram shows.
Frequency
Master
frequency 1
Master frequency
2 attained
Master frequency
attained
Output frequency
Frequency
command
Time
2Hz
4Hz
2Hz
2Hz
Master frequency
1 attained
Master
frequency 2