DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-90
coast to stop
Motor 1
Motor 2
Motor 3
Motor 4
V
FD-F operation
time
freq
by VFD-F
by VFD-F
by VFD-F
by VFD-F
Output Freq
by VFD-F
Acc Time
Pr01-09
Acc Time
Pr01-09
Acc Time
Pr01-09
Acc Time
Pr01-09
Acc Time
Pr01-09
Pr11-03 Pr11-04 Pr11-03 Pr11-04 Pr11-03 Pr11-04 Pr11-03 Pr11-04
Pr11-03 Pr11-04
Off
Off
Off
Off
Off
Off
Off
Additional information on Circulative Control
Pr11-01=01 Fixed Time Circulation
After Motor#1 follows Pr11-03 <Fixed Time Circulation Setting> to run for some time, it will park freely. Then
Motor # 2 will wait for the Pr11-04<Motor Switch Delay Time> and start to run. The order to run of fixed time
circulation is Motor1-Motor2-Motor3-Motor4-Motor1-Motor2-Motor3-Motor4 repeatedly.
Setting of Related Parameters
Pr11-01=01 Select <Fixed Time Circulation>
Pr11-02=X Set quantity of motors, maximum 8 motors.
Pr11-03=X Set time for fixed time circulation.
Pr11-04=X Set time for motor switch delay time
.
Multi-function output terminal will follow Pr11-02 for setting.
Pr11-02= 01 02 03 04 05 06 07 08
Pr03-00= 1 1 1 1 1 1 1 1
Pr03-01= - 2 2 2 2 2 2 2
Pr03-02= - - 3 3 3 3 3 3
Pr03-03= - - - 4 4 4 4 4
Pr03-04= - - - - 5 5 5 5
Pr03-05= - - - - - 6 6 6
Pr03-06= - - - - - - 7 7
Pr03-07= - - - - - - - 8