5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-21
5.5 Group 4: Input Function Parameters
04 - 00
Multi-function Input terminal 1
Factory Setting: 01
04 - 01
Multi-function Input terminal 2
Factory Setting: 02
04 - 02
Multi-function Input terminal 3
Factory Setting: 03
04 - 03
Multi-function Input terminal 4
Factory Setting: 04
04 - 04
Multi-function Input terminal 5
Factory Setting: 05
04 - 05
Multi-function Input terminal 6
Factory Setting: 07
04 - 06
Multi-function Input terminal 7
Factory Setting: 08
04 - 07
Multi-function Input terminal 8
Factory Setting: 09
Settings 00~43
Setting Functions Descriptions
00 No function
All unused terminals should be set to 00, to assure
they have no effect on drive operation.
01 Multi-Speed terminal 1
02 Multi-Speed terminal 2
03 Multi-Speed terminal 3
04 Multi-Speed terminal 4
Allows selection of the 15 multi-step speeds. Please
refer to 05-00 to 05-14 to program the 15 step
speeds.
05 Reset (NO)
06 Reset (NC)
Clears (Reset) a fault and returns the AC drive to
normal operation.
When the AC Drive doesn’t work properly, this
terminal and the Stop/Reset key on the keypad
share the same function.
07 Jog operation (JOG)
This terminal and the JOG key on the keypad
share the same function.
When the AC Drive is functioning, this terminal
is disabled.
08 Accel/Decel disable
It stops the acceleration or deceleration of the AC
drive. AC drive then maintains a constant speed.
09 Accel/Decel 2 selection
10 Accel/Decel 3 selection
You can combine these two terminals and
choose between Acel/Decel time 1 to 4 in
Pr01-09 to Pr01-16.
Don’t do Accel/Decel time selection, but the
AC drive choose automatically Accel/Decel
time 1 as the Accel/Decel time
11 B.B. (NO) input
12 B.B. (NC) input
Enables the base block (pause) function.
Please refer to Pr.08-08, for base block functions.
13 Increase Frequency
This terminal shares the same function as the
Up/Down key on the keypad to adjust the master
Vista de pagina 53