5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-15
02-14 Source of Second Frequency Command
Factory
Setting
00
Setting
Range
00
Master Frequency Setting is controlled by PID
controller.
01
Master frequency is controlled by an external terminal via analog input
AVI: DC 0~+10V.
02
Master frequency is controlled by an external terminal via analog input
ACI1: DC 4~ 20mA.
03
Master frequency is controlled by an external terminal via analog input
ACI2: DC 4~ 20mA
04
Master frequency is handled via RS485 serial
communication (RJ-11).
05 External Reference Master frequency via External Reference.
This parameter sets the source of inverter’s second frequency.
02-15 Source of Second Operation Command
Factory Setting 00
Setting
Range
00 Controlled by the digital keypad
01 Controlled by the external terminals, keypad STOP enabled.
02 Controlled by the external terminals, keypad STOP disabled
03
Controlled by the RS-485 communication interface keypad STOP
enabled.
04
Controlled by the RS-485 communication interface keypad STOP
disabled.
This parameter sets the source of inverter’s second operation command.
02-16 Loss of ACI Signal
Factory Setting 0.00
Setting
Range
0.00-Highest operational frequency
This parameter sets the loss of ACI signal